If room temperature optimization is enabled, the view will show the current room
temperature as well as the room temperature target values for each operating mode.
1 Heating curve
2 Current operating
mode
3
Circuit flow
temperature and
target temperature
4
Heating circuit
pump speed (if the
circuit has its own
pump)
5 Schedule for
operating modes
6 Settings
7
The impact of
different operating
modes
8 Room temperature
Heating curve
The heating curve determines the flow temperature: the temperature of water pumped
into the heating circuit at different outdoor temperature points. Usually, the installation
company takes care of heating curve configuration.
The heating curve consists of six adjustable points. Curve values should be tuned in
during the first few heating seasons.
The impact of different operating modes
There are three operating modes for space heating:
Normal
,
Boost,
and
Reduced
(see section
Home or Away function and Schedules
).
No room temperature measurement available or
temperature optimization disabled
Room temperature measurement active and
temperature optimization enabled
Room temperature optimization disabled
The selected operating mode will either increase (+) or decrease (–) the target flow
temperature by a set amount. This influences room temperature indirectly, see the table
below.
16 (49)
M8004 2308EN