Security
Levels
Display Code:
Description:
Adjusting Range:
SV
Set point Value of Control
Alarm 1 Set Point Value. Dwell Time
Ramp Rate
Offset Value for Manual Reset
(Integral Time TI = 0)
Alarm 2 Set Point Value
Display Shift
Proportional Band of Output 1
Integral (Reset) Time of Output 1
Derivitive (Rate) Time of Output 1
Hysteresis of Alarm 1
Hysteresis of Alarm 2
Hysteresis of ON-OFF control
Low Scale of Range. Adjust for
your process
High Scale of Range. Adjust for
your process
Power Limit of Output 1
Power Limit of Output 2
Input Type Selection
Display Units
Resolution
Control Action of Output 1
Alarm 1 Mode
Alarm 1 Special Function
Alarm 2 Mode
Alarm 2 Special Function
Proportional Cycle Time of Output 1
Cooling Cycle Time
Cooling P Band
Dead Band for pB and CPB
Low scale to high scale value
Trip Point within High/Low scale or 0 - 9999 minutes (for Dwell Time)
0 - 99.99
°
F/minute (0 - 55.55
°
C/minute)
0 - 100%
Only functional if Integral is set to 0.
Trip Point within High/Low scale
-199
°
to 199
°
F (-111 - 111
°
C) (Refer to page 21)
0 - 360
°
F (0-200.0
°
C)
O: for ON-OFF control (Refer to Page 17)
0 - 3600 seconds
0 - 1000 seconds
0 - 19
°
F (0 - 11
°
C)
0 - 19
°
F (1 - 11
°
C)
0 - 19
°
F (1 - 11
°
C)
0 - 40
Minimum value for the selected Input (INPT) to High Scale (HISC)
Low Scale (LOSC) to maximum value for the selected Input (INPT)
0 - 100%
0 - 100%
= J Type T/C
= E Type T/C
= S Type T/C
= PT100 JIS
0 - 1V
= 1 - 5V
= K Type T/C
= B Type T/C
= N Type T/C
= 4-20 mA
= 0-5V
T Type T/C
R Type T/C
PT100 DIN
= 0-20 mA
0 - 10V
= degree C
= degree F
= process units (Engineering Units)
= No decimal point used
= 2 Digit decimal (only for Linear Voltage or Current Input)
= 1 Digit decimal
= Direct (Cooling) Action
= Reverse (Heating) Action
0
= Deviation High Alarm
= Deviation Band High Alarm
= Full Scale High Alarm
= Deviation Low Alarm
= Deviation Band Low Alarm
= Full Scale Low Alrm
= No Special Function
= Alarm with Hold Function
= Dwell Timer ON as Time Out
= Alarm with Latch Function
= Alarm with Latch & Hold Function
= Dwell Timer OFF as Time Out
Same as Alarm Mode 1
= No Special Function
= Alarm w/Hold
= Alarm w/Latch
= Alarm w/Latch & Hold
0 - 99 Seconds, 0 for Linear current/voltage output
0 - 99 Seconds, 0 for Linear current/voltage output
0 - 360
°
F (0 - 200
°
C)
-199 - 199
°
F (-111 - 111
°
C)
1
2
Default
Setting:
18
°
F
(10
°
C)
0.00
0.0
18
°
F
(10
°
C)
18
°
F
(10.0
°
C)
120
40
0
0
0
0
100%
100%
20
For Relay Output
20
For Relay Output
0
= Output 2 cooling
=
or
/Minutes
0
0
999
18
°
F
(10.0
°
C)
212
Interface Address
Table 5.3 Index Code (Menu) Descriptions (OPERATOR LEVEL)
Long Scroll
For convenience, parameters can be recorded on the next page.