background image

Initial Operation:

When the control has been wired you can apply power.
The display should indicate the model number, software
version and LED lamp illumination test.  The
temperature (or other process variable) as measured at
the sensor should be indicated by the PV display.  The
thermocouple is wired in reverse if the indicated
temperature decreases as the temperature at the
thermocouple increases.  While making initial settings
to configure the control, the set point should be lowered
to a value (eg. 30°F) to assure the heaters will not be
energized.  This will allow time to make any adjust-
ments of the parameters in the operators or engineering
level.

During this initial set-up, alarm points and other settings
can be made.  The low limit and high limit range set-
tings (Lo.SC) and (hi.SC) should be adjusted to your
process.  This sets the range (span) of the control.  The
set point cannot be adjusted out of this range.
Generally, for plastics processing and packaging, a
span of 0 - 800°F is common.  If oils are used, a lower
span such as 0 -300°F should be entered.

When the configuration settings have been made, you
can return to the PV/SV level.  Adjust the required
process set point.  The red “out” lamp should illuminate,
indicating the heaters have been powered.

Autotuning:

The autotune function “teaches” the controller the main
characteristics of the process.  It “learns” by cycling the
output on and off.  The process will oscillate around the
set point during autotuning.  Note the diagram below:

Adjust the set point to a lower value if overshoot
beyond the normal process value may cause damage.
The results are measured and used to calculate the
optimum PID values.  It should not have to be repeated
on the same process.  The autotune function starts by

depressing the      and       keys for 4 seconds; then
release.  The process value display will flash on and off
indicating the control is in the autotune mode.  No other
adjustments can be made to the system while the con-
trol is autotuning.  The control will finish autotuning by
itself and the correct PID values will be entered into the
control’s memory.

Autotuning will not function if the control has been con-
figured from PID to ON-OFF.  For electric heating PID is
usually recommended.

Autotuning may not give satisfactory results and hold a
close temperature on all applications.  If this occurs,
you can change the PID values manually using the
three charts in Figure 5.2 on the top of the next page
for a guide.  It is recommended to change only one
parameter at a time, so the results of that change can
be clearly noted.

Adjusting PID Parameters:

The PID parameters can be reviewed by operating the
scroll key and noting whether the values are reasonable
or not.  Examine the controller’s result.  Modify the PID
values until the control quality is acceptable.

ON-OFF Control:

On-off control action is recommended when continuous
cycling of the load cannot be used.  Examples are
mechanical solenoids, large contactors and valves.  For
on-off control, set the following parameters to zero:
proportional band; integral; derivative and offset (oFSE).
The hysteresis (hySE) adjustment is now used to set
the deadband.  The larger the hysteresis is set, the
larger the deadband will be.  A large deadband will
cause the contactor (or other device) to switch less
often, but the process will oscillate farther from the set
point.  This setting is measured in degrees.

Initial Period

Process Oscillates

Verifying period

PID Control

Smarter Logic + PID

Set Point

Value

PB, TI, TD

Obtained

Autotune Finished

oFSE Value

Obtained

TEMPERATURE

TIME

Process 

Value

Figure 5.1 Autotuning

Содержание ETR-9200

Страница 1: ...MANUAL NO 25 SOFTWARE VERSION 1 8 and HIGHER Model ETR 9200 AUTOMATIC TUNING SMARTER LOGIC Controller SMARTER SMARTER LOGIC LOGIC LOGIC INSTRUCTION MANUAL ...

Страница 2: ...ed tampering Two large 4 digit displays show process and set point values at a glance Precise 14 slope sensor lineariza tion self diagnostic capability cold junction compensa tion and 3 mode PID calculations are automatically exe cuted by the single chip microprocessor The wide selection of parameters values sensor types set points control modes alarm modes degrees C F and security codes are held ...

Страница 3: ...3 6 F 50 to 1370 C 2 C T Copper Constantan 454 to 752 F 3 6 F 270 to 400 C 2 C E Chromel Constantan 58 to 1382 F 3 6 F 50 to 750 C 2 C B Pt 30 RH Pt 6 RH 32 to 3272 F 5 4 F 0 to 1800 C 3 C R Pt 13 RH Pt 32 to 3182 F 3 6 F 0 to 1750 C 2 C S Pt 10 RH Pt 32 to 3182 F 3 6 F 0 to 1750 C 2 C N Nicrosil Nisil 58 to 2372 F 3 6 F 50 to 1300 C 2 C RTD PT 100 ohms DIN 328 to 752 F 0 72 F 200 to 400 C 0 4 C R...

Страница 4: ...0db Common Mode Rejection 120db Operating Ambient for Rated Accuracy 14 120 F 10 50 C Storage Temperature 4 160 F 20 70 C Humidity 5 90 RH non condensing Insulation 20M ohms min 500VDC Breakdown 2000V AC 50 60Hz 1 minute Shock 200m s2 20g Weight 4 oz 110 grams EMC Emission EN50081 1 EN61326 EN55011 class B EN61000 3 2 EN61000 3 3 EMC Immunity EN50082 2 EN61326 EN61000 4 2 EN61000 4 3 EN61000 4 4 E...

Страница 5: ...ted by fuses or circuit breakers rated at the minimum value possible All units should be installed inside a suitably ground ed metal enclosure to prevent live parts being acces sible to human hands and metal tools All wiring must conform to appropriate standards of good practice national and local codes and regulations Wiring must be suitable for the maximum voltage current and temperature ratings...

Страница 6: ... be the same gauge and material If the RTD is a 3 wire device install the two common wires of the RTD to terminals 13 and 14 If a 2 wire RTD is to be used install a jumper between terminals 13 and 14 See page 22 for instructions to re range the input to volts milli volts or milli amps 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 0 20mA 4 20mA V 0 10V RTD A B B T C PTA TC MV TC COM mA V MV 90 264 VAC 50 ...

Страница 7: ...M 1 Load 3A 240VAC Max for Relay 1A for Triac Alarms 1 2 3A 240VAC Max Hot Fuse Neutral Alarm 2 Alarm 1 Figure 4 4 Example of wiring connections for ETR 9200 1211 Single Relay Output No Alarms Figure 4 5 Example of wiring connections for ETR 9200 1221 Heating Output with dual alarms Typical Wiring Diagrams 12 13 14 A B B 3 Wire RTD Connection 12 13 14 A B B 3 Wire RTD Connection CAUTION SHOCK HAZA...

Страница 8: ...ree Phase Power Fuse Alarms 1 2 3 A 240VAC max Hot Neutral Alarm 2 Alarm 1 Three Pole DP Magnetic Contactor Figure 4 6 Example of wiring connections for ETR 9200 1221 Heating and Cooling with alarm Figure 4 7 Example of wiring connections for ETR 9200 1221 with three phase Delta heater load NOTE The use of motor starters in place of magnetic contactors should be avoided They have very large induct...

Страница 9: ...N L Heater Power Neutral Hot Fuse Heater Fuse Figure 4 8 Example of wiring connections for ETR 9200 1321 with SSR output with dual alarms Red T C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 OUT 1 Load 3 Amp 240VAC Max Power Input Hot Fuse Neutral ALM 1 ALM 2 Figure 4 9 Ramp and Soak 12 13 14 A B B 3 Wire RTD Connection 12 13 14 A B B 3 Wire RTD Connection ...

Страница 10: ... addition of a stirrer will help to eliminate thermal lag Since the thermocouple is basically a point measuring device placing more than one thermocouple in parallel will provide an average temperature reading and produce better results in most air heated processes Proper sensor type is also a very important factor in obtaining precise measurements The sensor must have the correct temperature rang...

Страница 11: ...ification Key 2 Verifies the display accuracy for various input types during calibration Press and Disables keypad operation to protect all parameters from being longer than 4 Lock Key tampered with seconds Press and Engineering Selects the Engineering level Scrolls through the Engineering Programs Level Key 1 Resets the control to its normal status Press and Reset Exit Key 2 Unlocks keypad operat...

Страница 12: ...f no entry is made Short Scroll returns to PV SV Short Scroll advances step by step through parameters in forward direction Short Scroll advances step by step through parameters in forward direction Short Scroll advances step by step through parameters in forward direction Short Scroll returns to PV SV See page 14 Short Scroll returns to PV SV Views parameters step by step in reverse order Exits p...

Страница 13: ...1 C 0 19 F 1 11 C 0 40 Minimum value for the selected Input INPT to High Scale HISC Low Scale LOSC to maximum value for the selected Input INPT 0 100 0 100 J Type T C E Type T C S Type T C PT100 JIS 0 1V 1 5V K Type T C B Type T C N Type T C 4 20 mA 0 5V T Type T C R Type T C PT100 DIN 0 20 mA 0 10V degree C degree F process units Engineering Units No decimal point used 2 Digit decimal only for Li...

Страница 14: ...SIS ON OFF ADDRESS LOW LIMIT OF RANGE HIGH LIMIT OF RANGE POWER LIMIT OUTPUT 1 POWER LIMIT OUTPUT 2 INPUT TYPE UNIT TYPE RESOLUTION CONTROL ACTION ALARM MODE 1 ALARM 1 SPECIAL FUNCTION ALARM MODE 2 ALARM 2 SPECIAL FUNCTION PROPORTIONAL CYCLE TIME COOLING CYCLE TIME COOLING PROPORTIONAL BAND DEADBAND CONTROL NO PARAMETER DATE Table 5 4 Parameter Record Sheet OPERATOR LEVEL Long Scroll ...

Страница 15: ...low only selected parameters to be adjustable and all the others to be locked out For example if only the set point is to remain un locked all the other parameters in level 0 can be moved to level 1 Then lock out level 1 and 2 Press the keys to exit the engineering level Manual Mode hand control Used if sensor fails Peak Process Value Stored minimum and maximum values Calibrate A D Converter Indic...

Страница 16: ...r Enters the updated security level of ASP1 Enters the updated security level of RAMP Enters the updated security level of DB Defines the status of the outputs if the sensor fails Select the status for Alarm 1 Alarm 1 ON Alarm 1 OFF Select the status for Alarm 2 Alarm 2 ON Alarm 2 OFF Select the status for Output 2 Output 2 ON Output 2 OFF Select Lock or Free for operator Security Level 0 Locks al...

Страница 17: ... of the deadband hySE Hysteresis of On Off Control This parameter defines the deadband when on off control is used and PID control has been disabled For on off control set Pb Ei and Ed to 0 The output on a relay control will not change state until the temperature is outside the deadband Note page 17 for further information Addr Interface Address For external communica tions with a computer Lo SC h...

Страница 18: ...on the same process The autotune function starts by depressing the and keys for 4 seconds then release The process value display will flash on and off indicating the control is in the autotune mode No other adjustments can be made to the system while the con trol is autotuning The control will finish autotuning by itself and the correct PID values will be entered into the control s memory Autotuni...

Страница 19: ...you obtain and become familiar with the following reference material Tuning of Indusrial Control Systems by A R Corripio ISBA 1 55617 253 20 Available from ISA Publications and Training Aids Phone 919 549 8411 This method should be performed with a temperature chart recorder Fig 5 2 Steady State Cycling TIME PV Process value PV Tc P Band Pb 1 7 Pc Integral Time ti Tc Derivative Time td 0 125 Tc PV...

Страница 20: ...es When the control is powered the process will climb at 20 degrees per minute to the set point of 475 F Once the set point temperature has been reached the soak timer begins counting After a time period of 30 minutes has elapsed the alarm relay 1 will open and the process temperature falls at an uncontrolled rate This process will repeat every time power has been switched off and on to the contro...

Страница 21: ... an alarm at start up The alarm is enabled only when the Process Value reaches the Set Point SV Latch and Inhibited Alarm A1 SF A2 SF When selected the alarm will stay active until the power is reset The alarm mode is only enabled when the Process Value reached the Set Point Value SV Cooling A2 SF Alarm 2 can be designated as a cooling output if heating and cooling operation is desired Hysteresis ...

Страница 22: ...ated is 330 degrees F In order to achieve that temperature the controlled value or the temperature at the sensor must be 375 degrees F Due to the design and position of the components of the system the sensor could not be placed any closer to the work Thermal gradients different temperatures are common and necessary to an extent in any thermal system for heat to be transferred from one point to an...

Страница 23: ...will increase the span between the heating and cooling set points The range of this adjustment is from 199 199 F 111 111 C Re ranging for Linear Process Inputs Select the type of input you wish to use from the input type list in the operators menu on page 12 This would correspond to the output of the sensor or trans mitter you are using If the front display is to read in engineering units instead ...

Страница 24: ...oom temperature is entered press the key for 4 seconds After the key is released the upper display will strobe indicating that the new value has been loaded into the memory 4 Press the key to view 5 The upper display should read 0 00 Close SW1 The upper display should now read 20 00 If the value is not 20 00 make sure that the current source is accurate After a value of 20 00 is dis played in the ...

Страница 25: ...of the other common causes of failures WARNING Incorrect parameters entered in menu Excessive electrical interference Line wires are improperly connected No voltage between line terminals Incorrect voltage between line terminals Connections to terminals are open missing or loose Thermocouple or RTD is open at tip Thermocouple or RTD lead is broken Shorted thermocouple or RTD leads Short across ter...

Страница 26: ...input mode selected Analog portion A D converter defective Reversed input wiring of sensor No heater power output incorrect output device used Output device defective Open fuse outside of the instru ment Output device shorted or power service shorted CPU or EEPROM non volative memory defective Key switch defective Operation of control incorrect Electromagnetic interference EMI or Radio Frequency I...

Отзывы: