Operation
OPM223/253
52
R233
Enter control gain
K
p
1.00
0.01 ... 20.00
See "P(ID) controller" section.
R234
Enter integral action
time T
n
(0.0 = no I-
component)
0.0 min
0.0 ... 999.9 min
See "P(ID) controller" section.
With every Hold, the I-component is set
to zero. Although Hold can be
deactivated in field S2, this does not
apply for Chemoclean and timer!
R235
Enter derivative
action time T
v
(0.0 = no D-
component)
0.0 min
0.0 ... 999.9 min
See "P(ID) controller" section.
R236
Select controller
characteristic
dir = direct
Inv = inverse
The setting is required depending on the
control deviation (upward or downward
deviation, see "Chemoclean function"
section).
R237
Select pulse length
or pulse frequency
len = pulse length
Freq = pulse frequency
Curr = current output 2
Pulse length e.g. for solenoid valve,
pulse frequency e.g. for solenoid dosing
pump, see "Actuating signal outputs"
section.
Curr = current output 2 can only be
selected if O2 = Contr.
R238
Enter pulse interval
10.0 s
0.5 ... 999.9 s
This field only appears if pulse length is
selected in R237.
If pulse frequency is selected, R238 is
skipped and entries continue with R239.
R239
Enter maximum
pulse frequency of
the adjuster
120 min
-1
60 ... 180 min
-1
This field only appears if pulse
frequency is selected in R237. If pulse
length is selected, R239 is skipped and
entries continue with R2310.
R2310
Enter minimum
switch-on time t
ON
0.3 s
0.1 ... 5.0 s
This field only appears if pulse length is
selected in R237.
R2311 Enter basic load
0 %
0 ... 40 %
When you select the basic load, you
enter the desired dosing quantity.
100% basic load corresponds to:
– Constantly on for R237 = len
– Fmax at R237 = feq
– 20 mA at R237 = curr
Coding
Field
Setting range
(Factory settings, bold)
Display
Info
R233
Kp
1
.
00
R234
min
Time Tn
0
.
0
R235
min
Time Tv
0
.
0
R236
Direction
dir
R237
Oper
.
Mode
len
R238
s
PulsePer
.
10
.
0
R239
1
/
min
Max
.
PFreq
120
R2310
s
Min.PTime
0.3
R2311
%
BasicLoad
0
Содержание OPM223