Details for Each Component
1. Positive, Negative Output Bus Bar
Bus Bar for Output Voltage and Current
2. Voltage Sensing Terminal Block
Voltage sensing terminal block. Rewards up to +5% of power supply’s maximum output voltage value.
A warning message is displayed on the LCD if the reward value exceeds 5%.
If the value exceeds 10%, power supply’s output is disabled.
3. RS232C/RS485 Connection Port
The IN connection port has a built-in RS232C,RS485 connection,
and the OUT port is for parallel RS485 connection.
4. RS485 Termination Switch
On/Off switch for using terminating resistors when using RS485 connection.
Turns on the 120 Ohm resistor for the RS485 data connection line when turned on.
5. AC Input Terminal Block
Terminal block for connecting the AC input. The Ground input is the default setting.
Input voltage: 3Phase 342Vac ~ 440Vac 60Hz
6. Signal I/O Terminal Socket
Refer to the MX-Series Option Manual.
7. Parallel Control Terminal Block
Terminal block for parallel current in case of using over 30kW.
2-3. Output Check
- 17 -