Adesys bv, Wateringen, NL
Operation instructions
Octalarm-T2 / T4 / T8 / T16
11
5. FUNCTIONING OF THE LOCAL ALERT
5.1 Alarm buzzers
In case of an alarm, the built-in buzzer will ring together with the buzzer(s) that may have been
connected externally. The conditions that enable and disable the buzzer can be set:
•
Enable immediately after detection of the alarm (factory default).
•
Enable after a set delay time.
•
Only enable if a telephone report has failed completely.
•
Disable automatically after a set delay time or at the moment the reset key is pressed.
•
Disable when the telephone report has passed off correctly (factory default).
•
Only disable at the moment the reset key is pressed.
The default start and stop conditions can be modified using the installation program. (See paragraph
18.5 Prog 31 “set alarm buzzer”
The volume of the internal buzzer can be adjusted from 0 up to 4 (factory default: 2). When connecting
the external buzzer (optional accessory, supplied by ADESYS), its volume can be adjusted to three
levels.
5.2 Flashlight
The Octalarm is equipped with a flashlight output (as option deliverable). As opposed to the alarm
buzzer, the flashlight cannot be turned off in the event of an alarm by using the reset key. The
flashlight can only be switched off by cancelling the alarm or by switching off the alarm selection key.
The flashlight reminds the user of the fact that the alarm has in fact been reset, but the cause is still
not resolved.