DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 5 to 20KVA rev 1-8.docx
II-55
II.2.2.21 Lonworks link (Option):
The lonworks interface use an FT10 module.
II.2.2.22 4-20mA outputs (Option)
II.2.3 4-20MA LOOP CURRENT :
The CCR can be delivered with two independent 4-20mA current loops with the following features :
•
The two outputs are isolated (500V~).
•
The load to be connected must be less than 200 Ohms.
•
I1 is connected to J10 (pin 1 = +, pin2 = -), I2 is connected on J11 (pin 1 = +, pin2 = -)
4-20mA outputs configuration
4-20mA output
Jbus
address
B7 B6 B5 B4 B3 B2 B1
B0
I1
➔
loop current, I2
➔
loop power
69
X
X
X
0
X
X
X
X
I1
➔
loop insulation, I2 not used
69
X
X
X
1
X
X
X
X