DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 5 to 20KVA rev 1-8.docx
II-49
II.2.2.15 Wiring remote control voltage configuration
The DIAM CCR can be remotely controlled either by an external voltage (20 to 60 VDC positive or
negative, or 120Vac), or by “free potential” contacts (internal power supply 30VDC from the CCR, or additional
120Vac source). This choice is made by the values at address 70 in the Jbus table.
CONTROL INPUTS CONFIGURATION
Inputs configuration
Fig
Jbus address
B7 B6 B5 B4 B3 B2 B1 B0
External v20V to +60V-- to
control the inputs
1
70
X
0
X
X
X
X
0
0
External voltage -20V to -60V-- to
control the inputs
2
70
X
1
X
X
X
X
0
0
Contacts to control the inputs.
24V-- internal voltage
3
70
X
0
X
X
X
X
0
1
FAA type only
. External voltage
115V~ to control the inputs
4
70
X
0
X
0
X
X
1
0
FAA type only
. Internal voltage 115V~
to control the inputs
5
70
X
0
X
0
X
X
1
0
IMPORTANT NOTICE :
This control inputs configuration, as other configuration elements, are set in factory according the kind
of remote control board and the type of control supply.
See the part number wrote on the identification plate to know the type of remote control delivered (end
appendix C: PART NUMBER IDENTIFICATION
at the end of the manual)