II.2.2.4 FAA Multiwire remote control with 20 to 60Vdc control supply
II.2.2.5 FAA Multiwire remote control with EXTERNAL 20 to 60Vdc control supply
When delivered, the CCR is configured in factory as :
-
Wiring remote control voltage configuration
-
Operating modes for multiwire (FAA & IEC) remote control :
- Default brightness B1 (2.8A)
- 1, 3 or 5 brightness, as ordered and indicated in the part number (see at the end
The 34-pin terminal blocks making up the inputs and outputs for remote control are situated at the back of
the CCR.
II.2.2.5.1
Inputs (20 to 60 Vdc only) :
Terminal
T.Bloc
Function
FAA label
Pin Type
1
T1
B1 control
B1
Input voltage with respect to C
2
T1
B2 control
B2
Input voltage with respect to C
3
T1
B3 control
B3
Input voltage with respect to C
4
T1
B4 control
B4
Input voltage with respect to C
5
T1
B5 control
B5
Input voltage with respect to C
6
T1
“ON” control
CC
Input voltage with respect to C
7
T1
Circuit 1 control (*)
Input voltage with respect to C
8
T1
Circuit 2 control (*)
Input voltage with respect to C
9
T1
Circuit 3 control (*)
Input voltage with respect to C
10
T1
Circuit 4 control (*)
Input voltage with respect to C
11
T1
Circuit 5 control (*)
Input voltage with respect to C
12
T1
Aux 1 control (**)
Input voltage with respect to C
13
T1
Aux 2 control (**)
Input voltage with respect to C
14
T1
C
CCI
Common to Pin1 to Pin 13 inputs
Notes :
FAA Labels
:
- CCI is the common of the external power supply (20 to 60Vdc) for all inputs (Pins 1 to 13).
- CC : when selected, the CCR goes to B1 (see
Operating modes for multiwire (FAA & IEC) remote control :
(*)
If there is a built-in circuit selector under the CCR (2 to 5 ways)
(**)
Not used : for special applications
The remote control
protection fuse
is marked as PFU2 on the interface board (5x20mm 250V/500mAT)