![OCEM AUGIER energy DIAM4200 Series Скачать руководство пользователя страница 27](http://html1.mh-extra.com/html/ocem/augier-energy-diam4200-series/augier-energy-diam4200-series_installation-and-maintenance_723485027.webp)
DIAM4200 ©2018 AUGIER SA.
6021642 DIAM4200 5 to 20KVA rev 1-8.docx
I-27
The active part of the protector can be replaced, in case of failure or short circuit due to particularly high
energy overvoltage.
I.8.4 CASTERS
CCRs can be delivered with or without chassis casters, preferably uni-directional (other models on
request)
I.8.5 BURNT LAMPS DETECTION:
This option determines the number of burnt lamps in the output load.
This is carried out by measuring the load Voltage versus Current phase shift.
Internal parameters of the data collection system must be re-initialised each time the loop is modified
(addition of transformers, replacement of transformers by more powerful ones, etc) or if any settings have
been changed (load adjustment, for example).
To increase the accuracy of the measurement, it is necessary to perform the calibration with
0
lamp
burned (1
st
stage) and
minimum 3%
of lamps burned (2
nd
stage).
Before perform the calibration, it
is necessary to set the following parameter in the menu “
Calibration
”:
The X number must be set in function of the total number of lamps in the loop to realize the calibration
(X can be set for 1 to 10 lamps).
Example: if the load loop is about 20 lamps, set the X parameter to 1 ( 1/20 = 5% > 3%).
Example: If the load loop is about 200 lamps, set the X parameter to 6 lamps. (6/200 = 3%).
Initialisation can be carried out in two stages:
1. The loop should be connected up to the CCR with
no
burnt lamp (all lamps are working).
Go into the “
Calibration”
menu then:
Press
OK
to start initialisation.
The message “
Wait please...”
blinks, meaning that data collection is in progress.
When the message stops flashing, data collection has been completed.
2. The loop should be connected up to the CCR with
X
lamp disconnected:
Go into the “
Calibration”
menu then
Press
OK
to start initialisation.
The message “
Wait please...”
flashes meaning that data collection is in progress.
When the message stops flashing, data collection has been completed.