II.2.2.16 Operating modes for multiwire (FAA & IEC) remote control
The device can be controlled in two ways:
•
“
Without ON order”,
with direct command of brightness levels. (preferred configuration)
•
“
With ON order
” and brightness selection
The choice is made by setting a parameter in the jbus table using ALIZE4100 software.
ON ORDER CONFIGURATION
Inputs configuration
Jbus
address
B7 B6 B5 B4 B3 B2 B1 B0
Without ON ORDER
69
X
X
X
X
X
X
X
0
With ON ORDER (B0
Brightness)
69
X
X
X
X
X
X
0
1
With ON ORDER (B1
Brightness)
69
X
X
X
X
X
X
1
1
Without ON order:
Activating input B0, B1,… B7 causes the device to start up at the selected brightness. The CCR stops 0.2s after
any order has stopped.
With ON order:
Activation of the “ON” input causes the CCR to start up at the preferred brightness defined (B0 or B1), if no
brightness level has been selected.
Brightness level is changed by adding the desired brightness input.
The CCR stops when the “On” order is stopped whatever the states of the brightness inputs.
The choice of B0 or B1 is configurable using the ALIZE4100 software. (B0 is the default value)