Maintenance & Information 

 

REPAIRS TO SEALED COMPONENTS 

1)  During  repairs  to  sealed  components,  all  electrical  supplies  shall  be  disconnected  from  the 

equipment being worked upon prior to any removal of sealed covers, etc. If it is necessary to 
have an electrical supply to equipment during servicing, then a permanently operating form of 
leak  detection  shall  be  located  at  the  most  critical  point  to  warn  of  a  potentially  hazardous 
situation. 

2)  Particular  attention  shall  be  paid  to  the  following  to  ensure  that  by  working  on  electrical 

components, the casing is not altered in such a way that the level of protection is affected. This 
shall include damage to cables, excessive number of connections, terminals not made to original 
specification, damage to seals, incorrect fitting of glands, etc. 

Ensure that apparatus is mounted securely. 

Ensure that seals or sealing materials have not degraded such that they no longer serve the purpose 
of preventing the ingress of flammable atmospheres. Replacement parts shall be in accordance with 
the manufacturer's specifications. 

NOTE: The use of silicon sealant may inhibit the effectiveness of some types of leak detection 
equipment. Intrinsically safe components do not have to be isolated prior to commencing works. 

DETECTION OF FLAMMABLE REFRIGERANTS 

Under no circumstances shall potential sources of ignition be used in the searching for or detection of 
refrigerant leaks. A halide torch (or any other detector using a naked flame) shall not be used. 

LEAK DETECTION METHODS 

The following leak detection methods are deemed acceptable for systems containing flammable 
refrigerants. 

Electronic leak detectors shall be used to detect flammable refrigerants, but the sensitivity may not be 
adequate, or may need re-calibration. (Detection equipment shall be calibrated in a refrigerant-free 
area.)  

Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. 
Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and shall be 
calibrated to the refrigerant employed and the appropriate percentage of gas (25 % maximum) is 
confirmed. 

Leak detection fluids are suitable for use with most refrigerants but the use of detergents containing 
chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe-
work.  

If a leak is suspected, all naked flames shall be removed/ extinguished. 

If a leakage of refrigerant is found which requires brazing, all of the refrigerant shall be recovered from 
the system, or isolated (by means of shut off valves) in a part of the system remote from the leak. 
Oxygen free nitrogen (OFN) shall then be purged through the system both before and during the 
brazing process. 

 

 

 

 

 

 

 

Содержание RAPID PRO RP14

Страница 1: ......

Страница 2: ...ur invoice as proof of purchase provide further information relating to the issue including any photos or videos have completed the online warranty registration or provide a completed warranty card On...

Страница 3: ...Note 5 Specifications 7 Modes Codes 8 Quick Start Guide 10 Safety 11 Location of Installation and Airflow Clearance 12 Installation Connection 16 Controller Operation 22 WiFi Settings 28 Troubleshoot...

Страница 4: ...ith minimal running costs Designed with the latest technology including stepless full DC inverter compressors fans and control systems the Oasis iX series is the energy efficient and environmentally f...

Страница 5: ...lar inspection of the condensate drain to detect any obstructions or debris accumulation It is important to keep the drain clean to allow for smooth condensate flow and proper discharge to the drainag...

Страница 6: ...4 9 COPat 50 capacity 7 2 7 5 7 2 7 4 7 4 7 4 7 4 COPat 20 capacity 7 9 8 8 8 0 8 8 8 1 8 1 8 0 Air 35 C Water 28 C Cooling capacity kW 6 3 9 0 10 0 11 3 15 0 15 0 19 5 Sound Pressure at 1m dB A 37 8...

Страница 7: ...G H RP14 402 574 389 432 945 340 73 660 RP16 402 674 389 432 1045 370 73 660 RP18 402 674 389 432 1045 380 73 660 RP22 402 824 389 432 1195 470 73 760 RP32 511 891 498 536 1264 570 73 956 RP32T 511 89...

Страница 8: ...20 Fast heating intelligent optimization according to ambient temperature and water temperature Energy efficiently saving Smart mode Heating capacity 100 20 Intelligent optimization according to ambie...

Страница 9: ...ainage point The unit must sit level to allow condensation to drain correctly The schematic diagram is for reference only Please check the water inlet outlet label on the heat pump while plumbing the...

Страница 10: ...t be running and water circulating through the heat pump for the system to operate 1 Turn on your water pump and check for water leaks and verify water flow to and from the pool 2 Turn on the electric...

Страница 11: ...system After a stoppage the unit will not start for at least 3 minutes Do not use any means to accelerate the defrosting process or to clean other than those recommended by the manufacturer If install...

Страница 12: ...nt space for unobstructed airflow into and out of the heater At least 3 5m away from the water s edge No greater than 7 5m from the water s edge to avoid heat loss from the piping No greater than 5 0m...

Страница 13: ...th the specifications on Page 5 of this manual Location Connect the unit in the pool pump discharge return line downstream of all filter and pool pumps and upstream of any chlorinators ozonators or ch...

Страница 14: ...nit Optimal water flow rates are listed on Page 5 of this manual It is imperative that water flow is kept as close as possible to these flow rates Correct water flow not only offers optimal heater per...

Страница 15: ...install the drainage barbs Condensate Drain Barbs Fit the condensate drain barbs into the 2 holes under the unit if you need to direct water away from the heater If the barb is too stiff place it in h...

Страница 16: ...onal circuit protection device must be installed between the heater and the water circulation pump if a water pump is hard wired into the heater Please note recommended circuit breaker sizes make no a...

Страница 17: ...r 3 seconds to unlock lock screen After screen is unlocked press it to select mode Auto 12 40 C 54 F 104 F Heating 18 40 C 64 F 104 F Cooling 12 30 C 54 F 86 F Speed Select Turbo Smart Silence mode Up...

Страница 18: ...splay Real time power consumption function available for single phase only Mode Selection Press to select mode Auto adjustable temperature range 12 40 C 54 F 104 F Heating adjustable temperature range...

Страница 19: ...n press once to cancel the setting Time display When the machine is off the time display on the top right corner is real time When the machine is on the real time can be shown 10 seconds if you press...

Страница 20: ...etting After setting the icon in the lower left corner indicates as below Timer on every day Timer off every day Timer on every day No timer off and alternate display Timer on every day Timer off one...

Страница 21: ...er the Parameter Modification mode press or to change the values then press to confirm and quit Parameter Modification mode press to quit Parameter Checking status No Content Adjust Range Step Length...

Страница 22: ...ll status points and their corresponding value through or Press to quit running status checking mode Symbol Content Unit C0 Inlet water temp C F C1 Outlet water temp C F C2 Ambient temp C F C3 Exhaust...

Страница 23: ...oting purposes App Installation To download simply visit your device s app store and search for Inverter Life App Set Up Create an Account In order to take advantage of the app you must first register...

Страница 24: ...IGURED AT 2 4 GHZ AND THE BLUETOOTH FUNCTION IS ENABLED Auto Discovery Bluetooth Press for 3 seconds after the screen unlock will be flashing rapidly to enter Wi Fi connection status Click Add Device...

Страница 25: ...screen unlocks will be flashing rapidly to enter Wi Fi connection status Click Add device and follow the instructions below to finish connection display on the screen once the Wi Fi connection success...

Страница 26: ...cess Note If it doesn t jump automatically click Confirm hotspot connection next NOTE If connect fails please make sure your network name and password are correct And your router mobile phone and devi...

Страница 27: ...Page 26 of 43 WiFi Settings Operation Menu The following instructions are for heat pumps with heating and cooling functions...

Страница 28: ...y members also want to control the device Once your family members also register on the app initially subsequent operations can be conducted by the administrator as follows The following pictures are...

Страница 29: ...aust temp protection EA Evaporator overheat protection only at cooling mode P0 Controller communication failure P1 Water inlet temp sensor failure P2 Water outlet temp sensor failure P3 Gas exhaust te...

Страница 30: ...Page 29 of 43 Troubleshooting WIRING DIAGRAM 1...

Страница 31: ...Page 30 of 43 Troubleshooting WIRING DIAGRAM 2...

Страница 32: ...Page 31 of 43 Troubleshooting WIRING DIAGRAM 3...

Страница 33: ...your local service agent details Should I check my unit regularly We recommend you check your unit regularly to avoid potential issues and damage to your heat pump What should I be checking regularly...

Страница 34: ...eres Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants i e non sparking adequately sealed or intrinsically safe PRESENCE OF FIRE EXTINGUISHER If any h...

Страница 35: ...cks and component inspection procedures If a fault exists that could compromise safety then no electrical supply shall be connected to the circuit until it is satisfactorily dealt with If the fault ca...

Страница 36: ...TECTION OF FLAMMABLE REFRIGERANTS Under no circumstances shall potential sources of ignition be used in the searching for or detection of refrigerant leaks A halide torch or any other detector using a...

Страница 37: ...nts are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders for holding the...

Страница 38: ...d operate in accordance with manufacturer s instructions h Do not overfill cylinders No more than 80 volume liquid charge i Do not exceed the maximum working pressure of the cylinder even temporarily...

Страница 39: ...ce contact Oasis on 1800 815 913 or via our Service Request page on our web site provide a copy of your invoice as proof of purchase provide further information relating to the issue including any pho...

Страница 40: ...viously unboxed unit s On Commercial Installations such as but not exclusively health clubs swim schools motels hotels and hydrotherapy parts and in field labour warranty the warranty period is limite...

Страница 41: ...ty does not cover the following a Natural Disasters hail lightening flood fire etc b Rust or damage to paintwork caused by a corrosive atmosphere c When a unit is installed by an unqualified person d...

Страница 42: ...ect s Its use is beyond the control of the author contributor publishers and distributors and should not be relied upon without consulting your local Professional for comprehensive advice This guide i...

Страница 43: ...Page 42 of 43 Notes...

Страница 44: ...u 1800 815 913 ABN 87 858 371 003 Head Office 6 8 Austral Place Hallam VIC 3803 New South Wales Unit 2 10 Boden Road Seven Hills NSW 2147 Queensland 11 Andy Court Upper Coomera QLD 4209 New Zealand Oa...

Отзывы: