TFTN 085-199 Installation and Operation Manual
83
Table 16-8 DHW Setup
–
Advanced Settings
Setting
Parameter
Range/Description
Factory
Setting
Tank On Differential
24.21.0
Sets how much the DHW storage tank temperature can drop
below target before initiating a DHW demand. Only applicable
when using a Tank Sensor. (Range = 0-36°F)
0
Modulation Setpoint
24.20.0
Boiler outlet water temperature target during DHW demands.
(Range = 68-190°F)
180°F
Modulation Setpoint
25.2.7
System water temperature target during DHW demands serviced
by a cascade system. Only applicable for Manager boiler, and
with DHW configured as Downstream IWH. (Range = 68-190°F)
180°F
DHW/CH Charging
Priority
24.5.9
Alternating
–
DHW and CH will not operate simultaneously.
Priority switches between DHW and CH at an interval defined by
the CH/DHW Shifting Priority Time (first priority is DHW); if set to
0, then DHW has priority indefinitely.
None-Alternating
–
DHW and CH operate simultaneously for the
period defined by the CH/DHW Shifting Priority Time. After the
time elapses, operation returns to Alternating until the end of
the DHW request.
None
–
DHW and CH can operate simultaneously indefinitely.
Only applicable for DHW Mode configured as Downstream IWH;
Upstream IWH configuration always functions as Alternating
Alternating
DHW/CH Charging
Priority Time
24.4.8
Determines how long a CH or DHW demand can last before the
priority is switched. A value of 0 keeps the priority with DHW
indefinitely. (Range = 0-720min)
45 min
System Pump
Activation Logic
24.4.6
Always Active
–
SYSTEM PUMP output (AUX1) turns on for both
CH and DHW demands (with DHW Mode set to Downstream).
CH Only
–
SYSTEM PUMP output (AUX1) only turns on for CH
demands.
CH Only
DHW Pump Overrun
Time
24.3.6
Sets the length of time the DHW PUMP output operates after a
DHW demand is satisfied. (Range = 0-255sec)
15sec
Anti-legionella
Function
24.5.4
This function prevents the formation of Legionnaires’ disease
bacteria which may develop in piping and IWHs at temperature
between 68°F and 104°F. When set to On, if the IWH
temperature stays below 138°F for over 100 hours, the boiler will
heat the water in the IWH until it reaches 149°F for 30 minutes.
Only applicable when a Tank Sensor is used.
Off
DHW Recirc Setpoint
24.20.6
See Table 16-7
115°F
Scheduling (DHW
Recirc)
24.5.7 &
24.5.8
Always
Active