TFTN 085-199 Installation and Operation Manual
61
6.
Configure System Sensor Input
–
menu of the Manager boiler, set Auxiliary Sensor 1 =
System Sensor; see Figure 11-5.
Figure 11-5 Configuring System Sensor Input
7.
Configure Settings
–
and WiFi
are managed by the Cascade Manager and need to
be set from the Manager boiler’s touchscreen display via the typical menus; see
to have the display walk you through the setup procedure.
NOTE:
If the cascade system is heating a Downstream IWH, it is necessary to set
(Cascade) = Downstream IWH (Tank Sensor or Aquastat) on the Manager boiler.
NOTE
: If connecting an Upstream IWH to an individual boiler configure the DHW Mode accordingly from the display
of the respective boiler. An Upstream IWH cannot be connected to the Manager boiler if the system includes a
Downstream IWH.
NOTE
: DHW settings Tank Setpoint (Comfort), Tank Setpoint (Reduced) and Scheduling are shared for Upstream and
Downstream IWHs and are adjusted from the display of the Manager boiler.
NOTE
: If using an external signal (0-10V) for modulation control of the Cascade power or setpoint temperature, set
menu of the Manager boiler accordingly.
Select
Setup
from the home screen
Select
from the Setup menu
Select
from the Tech Menu
Set Auxiliary Sensor 1 = System Sensor (at Manager boiler
only).