Installation and Operation Manual
TFTN 085-199
106
Figure 18-2 Boiler Temperature in Range
3.
No Response to a Central Heat Demand
–
if the boiler is not responding to a CH demand, i.e., Zone Status does not
show “Priority” or “Calling” and the pump symbol does not turn green (see Figure 18
-2), proceed as follows:
i.
Check the Operating Mode to make sure it is set to “Winter”; see Secti
ii.
Check the field wiring to the
T-STAT #1-3
inputs; verify that 24VAC is present on R and W. If 24V is preset on
R
but not on
W
, then the issue is with the thermostat. If 24V is not present on
R
, then check the 2 Amp blade-fuse
on the Low Voltage Connection PCB, see Figure 18-4.
NOTE
: if the 2 Amp fuse on the Low Voltage Connection PCB is blown, check for correct field wiring to
the T-STAT
#1-3
inputs.
iii.
Check the Zone Controller Fuses; see Figure 18-4.
4.
Boiler Turned Off Via On/Off Switch
–
if this message is shown on the Home Screen it means that the burner was
disabled via the on/off button at the top-right of the screen (see Figure 18-3); press the on/off button to enable the
burner.
Figure 18-3 Boiler Turned Off Via On/Off Switch
5.
No Power to Zone Outputs:
i.
Confirm that the jumper wire is connected between terminals
ZONE INPUT
and
120V
, or
ZONE INPUT
and
R
(for
24V loads); see Figures 12-2 & 12-3.
ii.
Check the Zone Output fused on the Control Panel; see Figure 18-4.
NOTE
: if the display is not indicating that the zone output is on, i.e., pump symbol does not turn green (see Figure 18-
2) then the boiler is not attempted to turn the zone output on.
NOTE
: zone outputs will not turn on if there is a priority demand for DHW.
Outlet Temp
–
if higher than ON temp
the burner will not attempt to reignite.
If using a System Sensor, the burner will
only attempt to reignite if the system
temp drops below the ON temp
–
check
the
screen to view the
system temp.
ON Temp
–
for the active zone with
screen for a summary of the ON
temperature for all zones.
Zone Status
–
summary of which zones
are calling and which have priority.
Green pump symbol signifies that the
zone is actively being serviced.
On/Off Button
–
background is grey
when burner is disable and is white
when burner is enabled. Press to
change setting.
Display gives this message when the
burner on/off button is set to disabled.