Error Code
Problem
Possible Remedy
Error
Type
150
–
Common flow
sensor overheat
System sensor reading >
210°F
Faulty wiring
–
check the wiring to the System sensor for
water or corrosion
Auto
reset
Faulty sensor
–
check for proper readings from the System
sensor (see Table 18-2).
1P1 1
–
Flow check failed
(Supply Temp Change
Fast)
Outlet T-rise >
12.6°F/sec
Normal operation
–
In systems with high and low
temperature zones this message may be appear serval
times as zones turn off and on.
Warning
1P2 1
–
Flow check failed
(Sensor Delta T Too
High)
Delta-T > 63°F
Normal operation
–
In systems with high and low
temperature zones this message may be appear serval
times as zones turn off and on.
Warning
1P3 1
–
Flow check failed
(Supply Temp Too High)
Inlet > Outlet temp by
18°F
Normal operation
–
In systems with high and low
temperature zones this message may be appear serval
times as zones turn off and on.
Warning
1P4
–
Low Water
Pressure
Water pressure reading
< 7 psi
Low water pressure
–
raise the water pressure to a
minimum of 12 psi
Warning
Faulty wiring
–
ensure the wire harness is connected to
the water pressure sensor. Check for broken wires
Faulty sensor
–
replace pressure sensor
203
–
DHW Sensor
DHW tank sensor
reading is invalid
Incorrect setting
–
DHW Mode is set as
“
Tank Sensor
”,
but
a tank sensor is not being used. Change DHW Mode
setting to
“
Aquastat
”
Warning
Tank sensor not connected
–
Connect IWH tank sensor to
DHW SWITCH/NTC
Faulty wiring
–
check the wiring to the Tank sensor for
water or corrosion
Faulty sensor
–
check for proper readings from the Tank
sensor (see Table 18-2).
209
–
Storage tank
overheat
Tank sensor temp >
175°F
Plumbing problem
–
Boiler water is circulating through
the IWH coil during CH serving
–
section
Warning
Tank sensor improperly installed
–
ensure the tank sensor
is fully inserted into the well of the tank in the proper
location.
Faulty wiring
–
check the wiring to the Tank sensor for
water or corrosion
Faulty sensor
–
check for proper readings from the Tank
sensor (see Table 18-2).
2P2
–
Anti-legionella
function not finished
Anti-legionella function
is not complete (to
reset, switch the power
to the boiler off/on)
Anti-legionella Function turned on
–
if the anti-legionella
function is not wanted, then set Anti-Legionella Function
= Off (see
Warning
Boiler setting to low
–
set DHW Modulation Setpoint =
Tank sensor improperly installed
–
ensure the tank sensor
is fully inserted into the well of the tank in the proper
location.
Faulty wiring
–
check the wiring to the Tank sensor for
water or corrosion
Faulty sensor
–
check for proper readings from the Tank
sensor (see Table 18-2).
Plumbing problem
–
verify that boiler water is circulating