Installation and Operation Manual
TFTN 085-199
108
Error Codes
There are various types of errors, some are blocking (i.e., Manual & Auto Reset type) and required intervention to restore
boiler operation, while others are informational (i.e., Warnings) and do not directly block boiler operation.
Error Types:
•
Manual Reset
–
(by selecting “Press to RESET”) or the
-> Active
Errors menu (by selecting “Press to reset active errors”) before the boiler will attempt to resume
normal
operation.
•
Auto Reset
–
block the boiler from firing but will reset automatically when the error condition is resolved.
•
Warning
–
are informational only and do not block the boiler from firing; however, the warning may be an
indication that certain functions are no longer operational and therefore need attention.
Table 18-1 Error Codes
Error Code
Problem
Possible Remedy
Error
Type
101 1
–
Overheat
Inlet or Outlet
temperature exceeded
210°F
Lack of water flow
–
verify that the pump is getting
powered and that there is proper water circulation.
Manual
Reset
Faulty wiring
–
check the wiring to the Inlet and Outlet
sensors for water or corrosion
Faulty sensor
–
check for proper readings from the boiler
Outlet and Inlet temp sensors (see Table 18-2).
Burner plate thermal
switch tripped
Remove wires from thermal switch and check switch for
continuity. If switch is open inspect the inside of the
combustion chamber for damaged or missing insulation.
DO NOT OPERATE THE BOILER!
102
–
Pressure sensor
error
Water pressure reading
< 7 psi
Low water pressure
–
raise the water pressure to a
minimum of 12 psi
Warning
Faulty wiring
–
ensure the wire harness is connected to
the water pressure sensor. Check for broken wires
Faulty sensor
–
replace pressure sensor
103 1
–
Flow check failed
(Return or Supply Temp
Changed Too Quickly)
Outlet or Inlet T-rise >
12.6°F/sec (3x in a row)
Lack of water flow
–
verify that the pump is getting
powered and that there is proper water circulation.
Manual
Reset
Faulty wiring
–
check the wiring to the Inlet and Outlet
sensors for water or corrosion
Faulty sensor
–
check for proper readings from the boiler
Outlet and Inlet temp sensors (see Table 18-2).
104 1
–
Flow check failed
(Return or Supply Temp
Changed Too Quickly)
Outlet or Inlet T-rise >
27°F/sec (3x in a row)
Lack of water flow
–
verify that the pump is getting
powered and that there is proper water circulation.
Manual
Reset
Faulty wiring
–
check the wiring to the Inlet and Outlet
sensors for water or corrosion
Faulty sensor
–
check for proper readings from the boiler
Outlet and Inlet temp sensors (see Table 18-2).
105 1
–
Flow check failed
(Sensor Delta T Too
High)
Delta-T > 63°F (3x in a
row)
Lack of water flow
–
verify that the pump is getting
powered and that there is proper water circulation.
Manual
Reset
Faulty wiring
–
check the wiring to the Inlet and Outlet
sensors for water or corrosion
Faulty sensor
–
check for proper readings from the boiler
Outlet and Inlet temp sensors (see Table 18-2).
Flow check failed
Inlet > Outlet temp by
18°F (3x in a row)
Reversed piping
–
verify that the water is flowing through
the boiler in the correct direction.
Manual
Reset
Lack of water flow
–
verify that the pump is getting
powered and that there is proper water circulation.
Faulty wiring
–
check the wiring to the Inlet and Outlet
sensors for water or corrosion