GB
Retain these installation, operating and maintenance instructions for the full duration of the operator
’
s service life!
•
Operating Instructions
These Operating Instructions describe how to use
the prodct properly and safely. The safety advice and
information as well as the accident prevention and
general safety regulations for the field of application
must be complied with.
(factory-set operating mode)
The garage door operator can be actuated by an
impulse generator such as hand transmitter, key
switch etc. It is only necessary to generate a short,
sharp impulse.
Operator starts up and causes the door to travel to
set open or closed travel limits.
The door stops.
Door continues to move but in opposite direction .
During adjustments, in the event of a power failure or
malfunctions, the door can be disengaged from the
operator by actuating the pull cord on the carriage
and then be operated manually.
If the door is to be operated manually over a longer
period of time, then the existing locking pin must be
inserted (see figure
). The door latches put out of
service for power operation must be refitted,
otherwise the door is not latched in the the closed
position.
In order to restore power operation, return the
locking pin to the parking position ( ) and put the
latches out of service.
After an impulse has been generated, the door
automatically latches with the door operator.
If the closing door encounters an obstruction, the
operator stops and causes the door to open to ist top
end-of-travel position in order to clear the
obstruction. During the last 2 seconds of the closing
cycle, the door only opens slightly, this being
sufficient to clear the obstruction but otherwise
preventing anyone from taking a look into the
garage.
If the opening door encounters an obstruction, the
operator stops immediately and reverses the
travelling direction for approx. one second.
Connection plan ( figure
)
Wicket door contact STOPA
An open wicket door stops the operator immediately
or prevents it from starting up.
All persons using the gate system
must be shown how to operate it
properly and safely.
Keep hand transmitters out of the reach
of children.
When the operator is being used, the
opening and closing phases must be
monitored. It must be ensured that
neither persons nor objects are located
within the gate
’
s range of travel.
•
Normal operation (0)
Functional sequence
•
Quick release
12
a
•
Internal safety device
•
External safety device
13
First impulse:
Impulse generated while door is moving:
Repeated impulse:
closes automatically.
An interruption of the photocell, causes the door to
stop while it is closing and causes it to move in
opposite direction. While the door is opening, an
interruption does not have any impact on the
movement.
Same function as operation mode (6). However, an
interruption of the photocell during the open phase of
the door causes the door to stop its open phase and
to start up the warning phase.
Same function as operation mode (6). However, a
generated impulse during the open phase of the door
causes the door to stop its open phase and to start up
the warning phase.
Automatic Closing (7)
Automatic Closing (8)
•
Maintenance / Checks
The door system must be inspected
and tested by a specialist company
prior to initial operation and at least
once a year thereafter.
Monitoring the force limit
Caution!
The operator control unit features a dual-processor
safety system to monitor the force limit.
The integral force cut-out is automatically tested at
each travel limit.
The door system must be checked prior to initial
operation and at least once a year thereafter. In the
process, the force limiting device (figure 20) must be
tested!
If the closing force is set too
high, persons can be placed at risk of
injury or property could sustain damage.
Tthe force limit for the opening cycle can be adjusted
in menu stage 5, the force limit for the closing cycle
can be adjusted in menu stage 6.
The cycle counters stores the number of opening or
closing cycles performed by the operator.
In order to read out the meter, keep the
button pressed for 3 seconds until a number is
displayed. The display throws out the values
beginning from the highest decimal place down to
the lowest one after another. In the end, a horizontal
line is displayed. Example: 3456 cycles, 3 4 5 6 -
•
Cycle counter
Light barrier (STOP B)
An interruption of the light barrier causes a stopping
and a reversal during the closing cycle. An
interruption of the light barrier during the opening
cycle makes no difference.
The lighting switches on automatically whenever a
start impulse is generated and switches off again
after the set time phase (factory setting approx. 90
seconds).
If a signal light for signalling the opening and closing
phases is installed, this flashes along with the lamp
in the operator as soon as a start impulse is
generated. The operator starts with a time delay in
accordance with the set warning phase (see menu
stage 7).
Programming further hand transmitters:
See menu stages 1 and 2 (figure 15 and 16).
Changing the battery: Check the polarity is correct!
Take out the battery. Insert a new battery. Be sure t o
pole correctly! Slide the cover back on.
In menu 9, another operating mode can be chosen.
For the setting applying to menu 9, see parantheses.
The ventilation position is designed to allow
ventilation of the garage. For this, the door is opened
approx. 10 cm.
Actuation as for normal operation. By pressing the
2 button on the hand transmitter or generating an
impulse via another device, the door can be brought
into the ventilation position from the open or closed
state.
The gate will close automatically after 60 min or can
be closed earlier by any impulse transmitter.
Instead of opening the door fully, the door can be
partially opened by approx. 1 m in order to provide
access to the garage.
By pressing the 2 button on the hand transmitter or
generating an impulse via another device, the door
can be brought into the partially open state from any
given position.
•
Lighting
•
Signal light
•
Hand transmitter
Empty batteries must be disposed of separately
(toxic waste)!
Normal operation for ventilation position (1)
Operation on a side-opening sectional door (2)
•
Further operating modes
•
•
nd
nd
Opening-Closing-Operation (5)
Functional sequence
Automatic Closing (6)
Same operation mode as one-way control. However,
the receiver remains plugged in the operator.
Operator starts up and causes the door to travel to
open travel limit.
No impact; door continues opening.
Door closes.
Door stops and opens again.
Generated impulses always cause the door to open.
After the open and warning phases of the door, it
Impulse is generated while door is closed:
Impulse is generated while door is opening:
Impulse is generated while door is open:
Impulse is generated while door is closing: