Notifier VGM NION UniNet 2000 Скачать руководство пользователя страница 4

4

Document 52002  VGM NION Instruction Manual Rev. A  09/11/02

WARNING 

Several different sources of power can be con-

nected to the fire alarm control panel.  Disconnect all sources of
power before servicing.  Control unit and associated equipment
may be damaged by removing and/or inserting cards, modules,
or interconnecting cables while the unit is energized.  Do not
attempt to install, service, or operate this unit until this manual is
read and understood.

CAUTION - 

System Reacceptance Test after Software

Changes.  To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after any
programming operation or change in site-specific software.  Re-
acceptance testing is required after any change, addition or de-
letion of system components, or after any modification, repair or
adjustment to system hardware or wiring.

All components, circuits, system operations, or software func-
tions known to be affected by a change must be 100% tested.  In
addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly
affected by the change, up to a maximum of 50 devices, must
also be tested and proper system operation verified.

This system  meets NFPA requirements for operation at
0-49° C/32-120° F

 

 and at a relative humidity of 85% RH - 93%

per ULC - (non-condensing) at 30°

 

C/86° F.  However, the useful

life of the system's standby batteries and the electronic compo-
nents may be adversely affected by extreme temperature ranges
and humidity.  Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal
room temperature of 15-27° C/60-80° F.

Verify that wire sizes are adequate for all initiating and
indicating device loops.  Most devices cannot tolerate more than
a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may

operate erratically or can be damaged when subjected to light-
ning-induced transients.  Although no system is completely im-
mune from lightning transients and interferences, proper ground-
ing will reduce susceptibility.  

Overhead or outside aerial wiring

is not recommended, due to an increased susceptibility to
nearby lightning strikes.  Consult with the Technical Services
Department if any problems are anticipated or encountered.

Disconnect AC power and batteries prior to removing or in-
serting circuit boards.  Failure to do so can damage circuits.

Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure.  When possible, make all
cable entries from the sides or rear.  Before making modifica-
tions, verify that they will not interfere with battery, transformer,
and printed circuit board location.

Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal re-
moval.

Though designed to last many years, system components
can fail at any time.  This system contains static-sensitive com-
ponents.  Always ground yourself with a proper wrist strap be-
fore handling any circuits so that static charges are removed
from the body.  Use static-suppressive packaging
to protect electronic assemblies removed from the unit.

Follow the instructions in the installation, operating, and
programming manuals.  These instructions must be followed to
avoid damage to the control panel and associated
equipment.  FACP operation and reliability depend upon proper
installation by authorized personnel.

WARNING: This equipment generates, uses, and can radiate
radio frequency energy and if not installed and used in accor-
dance with the instruction manual, may cause interference to
radio communications.  It has been tested and found to com-
ply with the limits for class A computing device pursuant to
Subpart B of Part 15 of FCC Rules, which is designed to pro-
vide reasonable protection against such interference when
operated in a commercial environment.  Operation of this
equipment in a residential area is likely to cause interference,
in which case the user will be required to correct the interfer-
ence at his own expense.

Canadian Requirements

This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications.

Le present appareil numerique n'emet pas de bruits radio-
electriques depassant les limites applicables aux appareils
numeriques de la classe A prescrites dans le Reglement sur
le brouillage radioelectrique edicte par le ministere des Com-
munications du Canada.

FCC Warning

Installation Precautions

Adherence to the following will aid in problem-free installation with long-term reliability:

Precau-L-4-2002.p65

Acclimate Plus™HARSH™NOTI•FIRE•NET™ONYX™, and VeriFire™ are trademarks, and FlashScan® and VIEW® are registered trademarks of NOTIFIER.
NION™ and UniNet™ are trademarks of NIS.  NIS™ and Notifier Integrated Systems™ are trademarks and NOTIFIER® is a registered trademark of Fire•Lite
Alarms, Inc.  Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation.  ARCNET® is a registered trademark of Datapoint
Corporation.  Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.  LEXAN® is a registered trademark of GE Plastics, a subsidiary
of General Electric Company.

www.PDF-Zoo.com

firealarmresources.com

Содержание VGM NION UniNet 2000

Страница 1: ...UniNet 2000 VGM NION Instruction Manual VGM NION Document 52002 09 11 02 Rev A Version2 52002 A ECN 02 232 www PDF Zoo com firealarmresources com...

Страница 2: ...2 Document 52002 VGM NION Instruction Manual Rev A 09 11 02 www PDF Zoo com firealarmresources com...

Страница 3: ...ns caused by escaping gas improper storage of flammable mate rials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate o...

Страница 4: ...efore making modifica tions verify that they will not interfere with battery transformer and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage...

Страница 5: ...nection to Vista Gateway Module 13 1 10 Software Replacement Upgrade Installation 13 Figure 1 10 NION Software Replacement 13 Section Two The VGM NION Explorer Plug In 15 2 1 NION Description 15 2 2 E...

Страница 6: ...ary Service UniNet consists of graphical workstations monitoring and controlling local or remote twisted pair or fiber optic networks Remote network monitoring is achieved through the use of a Buildin...

Страница 7: ...ck specific connec tions for details The NION connects two LonWorks networks and provides a single two way communication channel for data when connected to a Vista Gateway module The LonWorks network...

Страница 8: ...T1 U6 TB1 Serial Interface A NOTES It is recommended that the installer conform to local code requirements when installing all wiring All power connections must be non resettable Refer to the current...

Страница 9: ...SPB can be installed in the following environmental conditions Temperature range of 0 C to 49 C 32 F 120 F 93 humidity non condensing at 30 C 86 F 1 4 Cabinet Mounting Information NISCAB 1 Installati...

Страница 10: ...work interface Slow blink indicates network operation normal Off indicates network interface not functioning Fast blink indicates a network communication error Network Packet Blinks briefly each time...

Страница 11: ...igh speed network allows communication between field nodes and a Local Area Server or a BCI NION modules provide the communica tion links between monitored equipment and the network J1 SMX Connection...

Страница 12: ...iguration Each segment can support 64 nodes and with routers the system can be ex panded up to 200 nodes Data A Data B Twisted Pair FTXC PCA Figure 1 8 FTXC PCA Transceiver Wiring FTXC PCB FT 10 Trans...

Страница 13: ...teps 1 Disconnect all power to the NION SPB IMPORTANT Always exercise ESD precautions when directly handling the NION SPB or any other hardware 2 Place the flash modules in their respective sockets ac...

Страница 14: ...14 Document 52002 VGM NION Instruction Manual Rev A 09 11 02 NOTES www PDF Zoo com firealarmresources com...

Страница 15: ...he Network Follow the steps below to establish communication between the VGM NION and the network 1 After installing the NION hardware and making all wiring connections bind the VGM NION to the Echelo...

Страница 16: ...operties of the VGM will be updated in the plug in window to reflect a successful enrollment Refer to Figure 2 6 to see an example of what an enrolled VGM NION looks like 6 IMPORTANT If more VGM NIONs...

Страница 17: ...28B Security Panel ADEMCO Keypad VGM NION Node 003 Bound VGM NION Node 005 Unbound Keypad Loop NOTE Node 001 is now bound but it must be disconnected before enrolling the next VGM If VGM NIONs are all...

Страница 18: ...There may be occasions however when a plug in will need to be configured manually This is done using the NION Plug In Application Selection and Configuration form To access this form from the Worksta...

Страница 19: ...order for plug in applications to function they must be linked with the nodes or devices to which they corre spond In most cases this is done automatically and each recognized node is linked to the a...

Страница 20: ...on Partition icons Figure 2 5 VGM NION Related Workstation Device Icons There are four ways to direct the VGM NION to send commands to the Vista Gateway Modules 1 Right click device icon popup menus a...

Страница 21: ...dress of the pertinent Vista Gateway Module keypad This parameter must be property configured before the VGM NION will function user ID This is a custom defined field ranging from 2 to 150 that identi...

Страница 22: ...the Vista panel before they are accessible through the VGM NION Figure 2 7 VGM Right Click Menu Options Right click on the VGM entry in the hierarchy and the popup menu will be displayed Module Right...

Страница 23: ...aulted zones prior to the Arm Stay Arm Away partition Disarm Disarms the selected partition Figure 2 9 Partition Status Commands NOTE Refer to the appropriate Vista User Guide for more details on part...

Страница 24: ...Y PANIC_ALARM PROGRAM_ENTRY ARMED_INSTANT ARMED_MAXIMUM BATTERYTEST ZONE_BYPASS Supported Event Codes COMM COMMFLT NETWORK VISTA PANEL BATTERY PARTxx 01 08 BYPASSxx 01 08 ZONExx 01 99 TELCO1 BELL1 TEL...

Страница 25: ...Transceiver 11 12 M Mapping Plug ins With NIONs 19 Module Right Click Menu Options 22 N Network Connection 11 NION Power Requirements 11 NION SPB Connectors 9 Description 7 Diagnostic LEDs 10 PC Boar...

Страница 26: ...lug In Command Accesses 23 Supported Device Types 24 Supported Event Codes 24 T Transceivers 11 Network 12 U UniNet System Overview 7 Update 22 V VGM NION Binding 15 Cabinet Mounting Information 9 NIS...

Страница 27: ...27 Document 52002 VGM NION Instruction Manual Rev A 09 11 02 NOTES www PDF Zoo com firealarmresources com...

Страница 28: ...to NOTIFIER One Fire Lite Place Northford Connecticut 06472 1653 This writing constitutes the only warranty made by NOTIFIER with respect to its products NOTIFIER does not represent that its products...

Отзывы: