Document 52002 VGM NION Instruction Manual Rev. A 09/11/02
FTXC-PCA and FTXC-PCB Network Transceivers
When used by the FTXC transceiver, FT-10 allows up to 8,000 feet (2438.4 m) per segment in a point-to-point
configuration, up to 6,000 feet (1828.8 m) per segment in a bus configuration, or up to 1,500 feet (457.2 m) per
segment in a star configuration. Each segment can support 64 nodes, and with routers, the system can be ex-
panded up to 200 nodes.
Data A
Data B
Twisted Pair
FTXC-PCA
Figure 1-8: FTXC-PCA Transceiver Wiring
FTXC-PCB
FT-10 Transceiver
Header Connection
Electrical Termination
Jumper
Data B
Data A
FTXC-PCA
FT-10 Transceiver
Header Connection
Electrical Termination
Jumper
Data A
Data B
Figure 1-7: SMX Transceivers: FTXC-PCA and FTXC-PCB
For more information on
termination settings, refer
to the Network Installation
manual, 51539.