Multi Variable Heat Pump Floor and Ceiling Type Indoor Unit
9
Connect the drainage pipe properly, as shown in Fig 4.3.1.2.
Fig.4.3.1.2
4.3.2 Drainage pipe installation
(1) The diameter of the drainage pipe should be the same or larger than the connection pipes (PVC pipe,
outside diameter 17mm (11/16inch)
, thickness
≥
1.75mm
(1/16inch)).
(2) Keep drainage pipe as short as possible and sloping downwards at a gradient of at least 1% to prevent
forming air bubbles.
(3) Insert the drainage hose into drain socket, tighten the metal clamp securely.
(4) Warp the sealing pad over drain hose and metal clamp for heat insulation.
(5) Make sure to perform insulation work for all drainage piping in order to prevent any possible
condensation.
(6) Apply the suitable diameter for converging drainage pipe according to the operating capacity of the
unit,as show in Fig. 4.3.2.1.
Fig.4.3.2.1
ķ
- T -drainage pipes assembled by T-shaped joints
(7)
The horizontal pipe can’t be connected to vertical pipe in the same level; please select the connection
way as shown in following fig.
Fig. 4.3.2.2: Three-way connection of drainage pipe joints