Multi Variable Heat Pump Floor and Ceiling Type Indoor Unit
14
5.5 Connection of Wired Controller and Indoor Units Network
(1) Communication wire of indoor unit to outdoor unit (or indoor unit) is connected to D1, D2.
(2) Wired controller is connected to H1, H2.
(3) One indoor unit can connect two wired controllers. One must be set as master one and one as slave.
(4) One wired controller can control 16 indoor units maximum at the same time. (as shown in Fig. 5.5)