Start Up | 38
Information Screens
The NHRS has a “display menu” from which various operating parameters can be viewed. It is
not possible to change the values on the display level.
1.
Display level operation
a.
Call up the display level with <↑> or <↓>.
b.
<↓> next operating parameter.
c.
<↑> previous operating parameter.
d.
Exit the display level with <Menu>.
2.
Description of the operating parameters on the display level.
NOTE: The following describes the individual operating parameters that can be selected
using the keys <↑> and <↓>, after the display level has been called up.
a.
Steam Production
1.
Current, actual, and nominal value of steam production are displayed in
percentage of total output.
2.
Nominal value:
unit capacity
x
input signal value
.
3.
Actual value:
max unit capacity
x
input signal value
x
capacity limitation
If the internal controller is activated, only the actual value is shown. Under the following
conditions the actual value may differ from the nominal value: upon activation of the
heating power, if capacity limitation is active during the filling cycle of the steam cylinder.
b.
Analog Input
1. Current value of the signal applied to the analog input in [%] of its max value.
If the internal controller is active, the displayed value corresponds to the current air
humidity (% RH).
c.
Internal Controller
1. Internal controller activated (“on”)/deactivated (“off”).
2. Activated with transducer signal.
3. De-activated with demand signal.
Содержание NHRS 010-090
Страница 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Страница 27: ...Installation 24 On Off Control Wiring Figure 15 On Off Controls Figure 16 Digital On Off Humidistat ...
Страница 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Страница 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Страница 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Страница 47: ...Start Up 44 p Software Version 1 Displays software version for the steam humidifier q Unit Type ...
Страница 51: ...Maintenance and Servicing 48 Maintenance and Servicing 49 Minor Maintenance 51 Major Maintenance ...
Страница 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Страница 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Страница 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Страница 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...