47 | Start Up
Selecting an RH Setpoint
The optimum humidity setpoint depends on the reasons that a conditioned environment is
being humidified. The “ASHRAE Handbook – HVAC Applications” recommends specific design
relative humidities for specific applications. Also see NORTEC publication “When You Need
Humidity” (Form 124A) for more information on humidity settings.
Health and Comfort
- The benefit of humidity is most pronounced for health and comfort in the
40-60% range. A humidity setting of 40-50 % is recommended for this purpose to prevent over
humidifying.
Temperature Setback
- In cold climates it is often necessary to reduce the humidity level in a
conditioned environment to prevent build-up of condensation on the inside of exterior walls,
windows, and trim. It is highly recommended that the temperature setback function of the
NORTEC digital controls be used under these conditions to prevent damage from condensation.
The digital control with an outdoor temperature sensor installed will automatically setback the
humidity setpoint to correspond with outdoor temperature.
Duct High Limit
– The duct high limit is intended to prevent saturation and wetting in duct work
at high load conditions. NORTEC recommends a setting of 85% for the duct high limit. It may
be necessary to reduce this setting if the duct work is very cold or in contact with exterior cold
surfaces.
Note:
The job site design may have specified a setpoint chosen specifically for the site.
Refer to site documentation and where possible use setpoints specifically determined
for the site.
Содержание NHRS 010-090
Страница 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Страница 27: ...Installation 24 On Off Control Wiring Figure 15 On Off Controls Figure 16 Digital On Off Humidistat ...
Страница 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Страница 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Страница 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Страница 47: ...Start Up 44 p Software Version 1 Displays software version for the steam humidifier q Unit Type ...
Страница 51: ...Maintenance and Servicing 48 Maintenance and Servicing 49 Minor Maintenance 51 Major Maintenance ...
Страница 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Страница 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Страница 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Страница 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...