Installation | 22
External Controls
Control Wiring
The following information is relevant to all controls, factory supplied or otherwise. For wiring use
a minimum of 18 AWG and keep as short as possible. The NHRS humidifier can be operated
with a modulating input or as On/Off.
Control Location
Figure 13: Control Location (Duct Humidification)
Duct Humidification
1
Air Proving Switch
Locate so that it can sense air flow, or lack thereof.
2
Duct High Limit
NHRS operates with On/Off control.
Locate at least 10 feet (3.0 m) from steam distributor, or far enough that steam is
fully absorbed under normal conditions.
3
Humidity Control
NHRS can be modulating, On/Off, or a humidity sensor.
Can be located either in return air duct (preferred) or in room being humidified.
Mount in area representative of room humidity (draft, doorways, sunlight, or
overhang such as shelf can affect reading). Avoid placing near discharge diffuser of
humidified air.
4
Outdoor Temperature Sensor
Mount in area representing outdoor air temperature (makeup air duct, outside).
Caution:
Failure to wire the humidifier in accordance with the wiring instructions
could cause permanent damage. Such errors will void the warranty.
Содержание NHRS 010-090
Страница 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Страница 27: ...Installation 24 On Off Control Wiring Figure 15 On Off Controls Figure 16 Digital On Off Humidistat ...
Страница 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Страница 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Страница 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Страница 47: ...Start Up 44 p Software Version 1 Displays software version for the steam humidifier q Unit Type ...
Страница 51: ...Maintenance and Servicing 48 Maintenance and Servicing 49 Minor Maintenance 51 Major Maintenance ...
Страница 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Страница 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Страница 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Страница 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...