49 | Maintenance and Servicing
Minor Maintenance
The NHRS will indicate “minor maintenance due” with a yellow flashing LED and a
message on the LCD.
1.
Visual inspection must be performed before minor and major maintenance.
a.
Inspect all water and steam installations for possible leakage or damage.
b.
Inspect electrical installation for lose or frayed cables, as well as damaged
components.
c.
Inspect the condition of the unit cabinetry for damage.
d.
Survey the area surrounding the humidifier – make sure all clearances are met.
2.
Maintenance
a.
Manually drain the NHRS by pressing the drain button on the display.
b.
Turn the unit power to the “off” position.
c.
Switch the external electrical disconnect to the “off” position (open).
d.
Remove the screw that holds the front door on the cabinetry in place.
e.
Remove the Font Panel by sliding the panel upward and away from the unit.
f.
Confirm that the high voltage feed to the unit is off, then remove the high voltage
wires that connect to the top of the steam tank.
The heating elements will not be affected if they are connected to different power lines
when re-installed. When re-connecting heating elements, ensure a tight engagement
with a “click” of the connectors.
g.
Using a slotted screwdriver, loosen the gear clamps that hold the steam line in
place.
h.
Remove the steam line.
i.
Remove the zip-tie cylinder restraint.
j.
Lift the cylinder upward, then out of the front of the unit.
WARNING:
A qualified service person should perform all maintenance on the
humidifier and any other equipment provided by Nortec that requires maintenance.
NOTE:
Instruction and details concerning the maintenance of the Nortec equipment
must be observed and adhered to without fail. Only the maintenance documented
in this manual must be carried out.
WARNING:
The NHRS brings water up to boiling temperatures. The steam tank and
plumbing components may be hot. Allow the unit an appropriate amount of time to
cool before performing service.
WARNING:
High voltage! Disconnect main power before servicing the unit
Содержание NHRS 010-090
Страница 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Страница 27: ...Installation 24 On Off Control Wiring Figure 15 On Off Controls Figure 16 Digital On Off Humidistat ...
Страница 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Страница 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Страница 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Страница 47: ...Start Up 44 p Software Version 1 Displays software version for the steam humidifier q Unit Type ...
Страница 51: ...Maintenance and Servicing 48 Maintenance and Servicing 49 Minor Maintenance 51 Major Maintenance ...
Страница 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Страница 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Страница 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Страница 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...