11 | Installation
Blower Pack Clearance Requirements
For more information regarding the clearance requirements of the Remote Mounted Blower
Pack (P/N 2572615), refer to installation manual (document number 2572641).
Table 4: Clearances for Blower Packs on Low Speed*
Humidifier
Capacity
lb/hr (kg/hr)
Min. Frontal
Clearance
Inches (cm)
Min. Overhead
Clearance
Inches (cm)
Min. Left Side
Clearance
Inches (cm)
Min. Right Side
Clearance
Inches (cm)
Up to 30 (13.6)
132 (336)
12 (31)
12 (31)
12 (31)
30-100
(13.6-45.4)
Not
recommended
Not
recommended
Not
recommended
Not
recommended
Table 5: Clearances for Blower Packs on High Speed*
Humidifier
Capacity
lb/hr (kg/hr)
Min. Frontal
Clearance
Inches (cm)
Min. Overhead
Clearance
Inches (cm)
Min. Left Side
Clearance
Inches (cm)
Min. Right Side
Clearance
Inches (cm)
Up to 30 (13.6)
132 (336)
12 (31)
12 (31)
12 (31)
30-100
(13.6-45.4)
Not
recommended
Not
recommended
Not
recommended
Not
recommended
*NOTES:
Nominal Conditions: 72ºF (22.2ºC), 43% RH.
Low speed not recommended for 50-100 lb/hr humidifiers.
Blower Pack should not be installed near cold surfaces or where dew point may be reached.
Higher humidity or lower room temperature may result in longer absorption distances.
Содержание NHRS 010-090
Страница 6: ...3 Introduction Humidifier Components Figure 2 NHRS Humidifier Components ...
Страница 27: ...Installation 24 On Off Control Wiring Figure 15 On Off Controls Figure 16 Digital On Off Humidistat ...
Страница 28: ...25 Installation Figure 17 Duct Sensor Wiring ...
Страница 30: ...27 Installation Figure 20 Digital Wall Humidistat Remote Wall Sensor ...
Страница 31: ...Installation 28 Transducer Control Wiring Figure 21 Transducers Figure 22 Digital Transducers ...
Страница 47: ...Start Up 44 p Software Version 1 Displays software version for the steam humidifier q Unit Type ...
Страница 51: ...Maintenance and Servicing 48 Maintenance and Servicing 49 Minor Maintenance 51 Major Maintenance ...
Страница 58: ...55 Troubleshooting Wiring Diagrams Figure 34 Wiring Diagram NHRS 010 to 090 ...
Страница 59: ...Troubleshooting 56 Figure 35 Wiring Diagram NHRS 135 to 180 ...
Страница 65: ...Spare Parts 62 NHRS Plumbing Parts Figure 36 Exploded view NHRS plumbing parts ...
Страница 67: ...Spare Parts 64 NHRS Electrical Parts Figure 37 Exploded view NHRS electrical parts ...