Pro-Meter V2K
8. From the Level 2 Setup Screen proceed to the
Position Sensor Calibration
Screen and establish the
following values in the highlighted (yellow) data entry fields:
Position Sensor Full Scale (mm) = 160.0
Zero Offset (mm) = 0.0
Bar Graph Max Pos (mm) = 144.0
Bar Graph Min Pos (mm) = 0.0
9. With the rods fully advanced (air cylinder retracted) enter the number reflected by the CURRENT MA
READING data display into the FULL SCALE MM CAL VALVE data entry field.
NOTE
: The linear position sensor should now be calibrated.
10. With the rods fully returned, utilize a 6 mm wrench, or equivalent tool, and close the gap between the
stop block and the carriage stop bracket.
NOTE:
There should be an audible click just before the gap closes completely.
11. Turn OFF MANUAL MODE via the
Dispense 1
Screen.
12. Adjust the strike stop position via the strike screw nut until the strike stop position produces the desired
shot size.
13. Be sure to tighten the stroke adjustment screw jam nut.
9