5 Parameter
BU 0135 en-4118
89
P420
Digital inputs
RF
Setting range
0 … 9
Other applicable parameter(s):
P130, P428
Arrays
[-01] = Digital input 1
(= value for digital input DIN1)
[-02] = Digital input 2
(= value for digital input DIN2)
[-03] = PTC input
(= value for PTC input TF)
[-04] = Bus In bit 0
(= value for Bus In bit 0)
[-…]
…
[-07] = Bus In bit 3
(= value for Bus In bit 3)
Factory setting
{ [-01] = 1 }
{ [-02] = 2 }
{ [-03] = 8 }
{ [-04] = 3 }
{ [-05] = 4 }
{ [-06] = 7 }
{ [-07] = 9 }
Description
Assignment of functions for the various digital inputs.
Note
In order to change parameter values,
P130
=1 must be set. Otherwise the settings of
P420
can only be read.
Non-permissible settings are ineffective and are not saved.
The parametrisation of array [-03] cannot be changed.
Arrays [-04 … -07] are only active for SK 175E devices.
Setting values
Value
Meaning
0
No function
The input is not used.
1
Enable right
The drive runs with a right-hand direction of
rotation.
(only for array [-01 and -02])
High active
Flank 0
1
1)
2
Enable left
The drive runs with a left-hand direction of
rotation.
(only for array [-01 and -02])
High active
Flank 0
1
1)
3
Enable right via bus
The drive runs with a right-hand direction of
rotation.
(only for array [-04 ... -07])
High active
Flank 0
1
1)
4
Enable left via bus
The drive runs with a left-hand direction of
rotation.
(only for array [-04 ... -07])
High active
Flank 0
1
1)
5
Disable voltage (coast to stop)
Drive runs down to a standstill.
Low active
6
Emergency stop
Drive switches to "Switch=on block" after
switching off (termination of selected switch-off
mode).
Low active
7
Fault acknowledgement
Acknowledge fault message.
Acknowledgement only possible if the cause of
the message is not longer present.
Flank 0
1
8
PTC resistor input
For evaluating a PTC signal.
High active
9
Release the brake
The brake is released manually (signal "high")
or automatically (signal "low")
High active
1)
If DIP switch 1 (
S1
) or parameter
P428
are parametrised to "Automatic Start-up" depending on
parameter
P130
, no flank is required. A "High Level" is sufficient.
P427
Emerg. stop Fault
FL
Setting range
0 … 1
Other applicable parameter(s):
P108, P130, P428
Factory setting
{ 0 }
Description
Emergency stop fault
-
decision as to how the motor starter should react in the event
of an error.
Setting values
Value
Meaning
0
Off
An error leads to immediate motor starter shut-off (motor runs
down to a standstill and brake, if present, is applied immediately)
1
On
With errors
E2.0, E3.0, E5.1, E6.1
the drive is run down in the
selected switch-off mode before the motor starter shuts off with an
error message.
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...
Страница 120: ...6071302 4118...