4 Commissioning
BU 0135 en-4118
67
Switch-off mode 2
DIP3/4
: OFF/ON
or
P108
= 1
Switch on
(Set enable)
1.
P3
and
P210
determine the starting voltage
(starting torque) that is applied to the motor.
2. The brake opens.
3.
P4
and
P102
determine the duration for which
the voltage is continuously increased until the
full voltage (100 %) is reached.
Switch off
(Cancellation of
release)
1.
P3
and
P210
determine the voltage (torque)
to which the motor controller immediately
drops.
2.
P4
and
P103
determine the duration for which
the voltage would be continuously reduced
from 100 % to 0 %. However, only the part of
the duration that is needed to reduce from the
set starting voltage (
P3
or
P210
) to 0 % is
used.
1)
3. The brake is applied when the voltage
reaches "0 %" or after
P107
has elapsed.
1)
For technical reasons, the motor starter switches immediately to 0 % when approx. 10 % of the starting voltage is reached.
Switch-off mode 3
DIP3/4
: ON/OFF
or
P108
= 2
(Factory setting)
Switch on
(Set enable)
1.
P3
and
P210
determine the starting voltage
(starting torque) that is applied to the motor.
2. The brake opens.
3.
P4
and
P102
determine the duration for which
the voltage is continuously increased until the
full voltage (100 %) is reached.
Switch off
(Cancellation of
release)
1. The motor is switched off immediately
(voltage "0 %") and runs down to a standstill.
2. The brake is applied when the voltage
reaches "0 %" or after
P107
has elapsed.
Switch-off mode 4
DIP3/4
: ON/ON
or
P108
= 3
Switch on
(Set enable)
1.
P3
and
P210
determine the starting voltage
(starting torque) that is applied to the motor.
2. The brake opens.
3.
P4
and
P102
determine the duration for which
the voltage is continuously increased until the
full voltage (100 %) is reached.
Switch off
(Cancellation of
release)
1. The motor is switched off immediately
(voltage "0 %") and runs down to a standstill.
2.
P4
and
P103
determine the duration of the
delay, during which the brake is not yet
applied.
3. The brake is applied.
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...
Страница 120: ...6071302 4118...