6 Operating status messages
BU 0135 en-4118
103
21.2
ADU error
"Overrun"
21.3
PMI error
"Access Error"
21.4
Userstack overflow
Warning messages
Display in the
SimpleBox /
ControlBox
Warning
Text in the ParameterBox
Cause
•
Remedy
Group
Details in
P700 [-02]
C002
2.0
Overtemp. Motor PTC
"Overtemperature motor
thermistor"
Warning from motor temperature sensor (triggering
threshold reached)
• Reduce motor load
C003
3.0
I
2
t overcurrent limit
Warning: I
2
t limit
e.g. output current > nominal current of motor
Reaching 1.3 times the nominal motor current for the
duration of 60 s.
• Continuous motor overload
Switch-on block messages
Display in the
SimpleBox /
ControlBox
Reason:
Text in the ParameterBox
Cause
•
Remedy
Group
Details in
P700 [-03]
I000
0.1
Disable voltage from IO
If the "disable voltage" function is parametrised, input
(P420 / P480) is Low
• "Set High" input
• Check signal cable (broken cable)
0.3
Disable voltage from bus
• Bus operation (P509): control word Bit 1 is "Low"
0.5
Enable on start
Enable signal (control word, Dig I/O or Bus I/O) was already
applied during the initialisation phase (after mains "ON", or
control voltage "ON").
• Only issue enable signal after completion of
initialisation (i.e. when the FI is ready)
• Activation of "Automatic Start" (P428)
With 3-phase devices: One phase is missing or not
connected.
I006
6.0
Mains voltage error
• Mains voltage failure
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...
Страница 120: ...6071302 4118...