NORDAC START (SK 135E / SK 175E) – Users Manual for Motor Starters
94
BU 0135 en-4118
P570
Locking time
RF
Setting range
0 … 25.50 s
Other applicable parameter(s):
P102, P103, P108, P130
Factory setting
{ 0.50 }
Description
The locking time determines the period of time during which the motor is not powered
after the end of the run-down time and before the acceleration time started in the
event of a change of rotating direction (reversing).
Note
As long as parameter
P130
=0 is set, the locking time is determined via potentiometer
P2
. In this case the parameter can only be read, but not changed. It then corresponds
to the setting determined by the potentiometer.
If the locking time is insufficient, the motor may still be rotating at the end of the run-
down time. Starting in the opposite direction of rotation would result in the motor being
subjected to excessive loads (thermal, mechanical) because of the counter-current
braking that occurs as a result.
P580
Error in the event of overtemp.
RF
Setting range
0 … 1
Other applicable parameter(s):
P108, P427
Factory setting
{ 1 }
Description
Fault shut
-
off due to overtemperature
– selection of whether an over temperature error
(PTC) should lead to a warning or a fault shut-off.
Setting values
Value
Meaning
0
Off
Warning (
C002
) due to overtemperature
1
On
Fault message (
E002
) and shut-off of device due to
overtemperature
P581
Phase sequence detection
RF
Setting range
0 … 1
Other applicable parameter(s):
P130, P428
Factory setting
{ 0 }
Description
Analysis of phase sequence of supply network by the device and automatic adaptation
of rotary field of motor to the required direction of rotation.
Note
As long as parameter
P130
=0 is set, phase sequence detection is determined via the
DIP switch
S1-DIP2
. In this case the parameter can only be read, but not changed. It
then corresponds to the setting that is determined by the DIP switch.
Setting values
Value
Meaning
0
Off
The direction of rotation of the motor is determined by the direction
of rotation of the supply network.
1
On
The direction of rotation of the motor is determined by the enable
direction.
P582
Manual brake release
RF
Setting range
0 … 1
Other applicable parameter(s):
P420
Factory setting
{ 0 }
Description
Definition of conditions for releasing a connected electro-mechanical brake
Note
DANGER!
With certain drive tasks (e.g. lifting gear) it can be dangerous to release of
the brake without the drive running (risk of raised load falling)!
Setting values
Value
Meaning
0
Off
The brake is only released if the motor is enabled.
1
On
The brake is released even if the motor has not been enabled (e.g.
if a drive is to be moved for revision work).
Pay attention to note!
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...
Страница 120: ...6071302 4118...