6.4 FAQ operational problems
Fault
Possible cause
Remedy
Device will not start (all LEDs
off)
• No mains voltage or wrong mains
voltage
• No 24 V DC control voltage
• Check connections and supply
cables
• Check switches / fuses
Device does not react to
enabling
• Control elements not connected
• Right and left enable signals present
simultaneously
• Enable signal present before device
ready for operation (device expecting a
0
1 flank)
• Restart inhibit is active
• Blocking time for reversing is active
• Reset enable
• Change over P428 if
necessary: "0" = device
expects a 0
1 flank for enable
/ "1" = device reacts to "Level"
Danger: Drive can start up
independently!
• Check control connections
• Check P130
• Check DIP switch S1-DIP1
Motor will not start in spite of
enable being present
• Motor cables not connected
• Brake not ventilating
• Check connections and supply
cables
Device switches off without
error message when load
increases (increased
mechanical load / speed)
• Mains phase missing
• Check connections and supply
cables
• Check switches / fuses
Motor rotating in wrong
direction
• Motor cable: U-V-W interchanged
• Motor cable Switch 2 phases
• Alternatively:
– Swap parameter
P420
functions right / left enable
Table 13: FAQ operational problems
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...
Страница 120: ...6071302 4118...