NORDAC START (SK 135E / SK 175E) – Users Manual for Motor Starters
70
BU 0135 en-4118
Features
• Electrically isolated bus interface
• Status display (1 LED)
• Configuration, optionally via
– integrated potentiometers and DIP switches
– or by means of parametrisation
• 24 V DC supply of integrated AS-i module via yellow AS-i cable
• 24 V DC supply to the motor starter
– via yellow AS-i cable (factory setting)
– or separately via black cable or another 24 V DC source – e.g. SK xU4-24V-… power supply (configurable
with jumpers)
• Connection to device
– via terminal strip
– or via M12 flanged connectors
Technical data for AS interface
Designation
Value
Jumper position "AUX"
Jumper position "AS-I"
Supply via AS-i (yellow cable)
26.5 – 31.6 V DC,
max. 25 mA
26.5 – 31.6 V DC,
max. 240 mA
1)
AUX supply (black cable)
24 V DC ± 25 %, max. 400 mA
Connection not permitted
Slave profile
S-7.A
S-7.A
I/O-Code
7
7
ID Code
A
A
External ID Code 1 / 2
7
7
Address
1A – 31A and 1B - 31B
(Delivery condition: 0A)
1A – 31A and 1B - 31B
(Delivery condition: 0A)
Cycle time
Slave
Master ≤
10 ms
Master
Slave ≤
21 ms
Slave
Master ≤
10 ms
Master
Slave ≤
21 ms
Quantity of (BUS I/O)
4I / 4O
4I / 4O
1)
Of which max. 165 mA is for peripherals (initiators, connected parametrisation tool, actuators)
4.3.3 Bus structure and topology
The AS Interface network must be set up in any form (line, star, ring and tree structure) and is
managed by an AS interface master as the interface between the PLC and slaves. Additional slaves
can be added to an existing network at any time, up to a limit of 31 standard slaves or 62 A/B slaves.
The slaves are addressed by the master or an appropriate addressing device.
An AS-i master communicates independently and exchanges data with the connected AS-i slaves.
Normal power units may not be used in the AS interface network. Only a special AS interface power
unit may be used for the power supply for each AS interface connector. This AS interface power
supply is directly connected to the yellow standard cable (AS-i(+) and AS-i(-) cable) and should be
positioned as close as possible to the AS-i master in order to keep the voltage drop small.
In order to avoid problems, the
PE connection of the AS interface power supply
(if present)
must
be earthed
.
The brown
AS-i(+)
and the blue
AS-i(-)
wire of the yellow AS interface cable
must not be earthed
.
Содержание NORDAC START Series
Страница 1: ...BU 0135 en NORDAC START SK 135E SK 175E Users Manual for Motor Starters...
Страница 4: ...NORDAC START SK 135E SK 175E Users Manual for Motor Starters 4 BU 0135 en 4118...
Страница 111: ...8 Additional information BU 0135 en 4118 111 8 1 4 EU Declaration of Conformity...
Страница 119: ...Key word index BU 0135 en 4118 119...
Страница 120: ...6071302 4118...