-6-
START-S19
Operating guide
1.9
Connection of STOP devices
Connection of the safety devices requires the use of any push-button or
N.C. (normally closed) contact. When there are several safety devices,
they are connected in series.
Connection of the STOP control
Push-button: stops and temporarily prevents all control unit function un-
til it is pressed again.
Switch: keeps the automation blocked until it is reset.
6 7 8 9 10 11 12 13 14 15 16 17
S 15
STOP Input
1 - activated
0 - Deactivated
If the input STOP
Is not used set up S15 at 0
!
1.10 Connection of the START command
The START opening command can be connected to any push-button or N.O.
(normally open) contact. If several devices are used, they must be connected.
Using terminals 13 and 15 it is possible connect a TIMER to program gate ope-
ning. The timer contact must be an NO (normally open) contact and must remain
closed for as long as the gate remains open. If an opening command is con-
nected to terminal 13, it must be connected in parallel.
The connection of the partial opening command can be done
with every button or NO contact.
6 7 8 9 10 11 12 13 14 15 16 17
Command
START
1.11
Connection of a Partial Opening
Command
12 13 14 15 16 17
20 21 22 23
Part. Opening
Command
If you use the antenna cable
for the 433.92Mhz frequency,
cut uit at 17cm and connect it
to the terminal no.17.
Connet the antenna wiring only after the
memorisation of the remote controls!
1.12 Connection of the
ANTENNA
12 13 14 15 16 17