-4-
START-S19
Operating guide
1.2
Connection of the power supply
The power supply line mast be protected from a magnetic-thermal switch or from a couple of 5A fuses. A diff erential
switch is recommended if it is not available in the installation
34
32 33
R
T
S
35 36 37
34
32 33
R
T
S
35 36 37
34
32 33
F
N
35 36 37
FOR THREEPHASE 400 Vac
FOR THREEPHASE 230 Vac
FOR SINGLEPHASE 230 Vac
Here is the connections of the inputs of the power network
32
,
33
and
34
and the set up in the terminals
35
,
36
and
37
.
1.3
Connection of the motor
1 2
4 5
3
W
U
V
1 2
4 5
3
Common
Open
Close
THREEPHASE motor
SINGLEPHASE motor
1.4
Connection of a 230 Vac SIGNAL LIGHT
27 28 29 30 31 32
• With fl ashing elec.card
27 28 29 30 31 32
38 39 40
• Without fl ashing elec.card
1.5 PRE-LIGHTING
It is possible to increase or reduce the pre-
lighting time when the gate is open or close.
Use
T05
and
T06
as reported:
t 05
t 06
PRE-LIGHTING BY CLOSED GATE
Set up from 0 to 10 s
Standard Value 2 s
PRE-LIGHTING BY OPEN GATE
Set up from 0 to 10 s
Standard Value 2 s
If you use the TEST for the photocells,
or a 24V light, you cannot use this connection.
!