Instruction Manual
OCM F
page 24
OCM F - rev. 05 / 06.04.2018
•
Low-impedance connection exists between '0 V DC' and GND analog output.
•
GND digital input, GND analog input and GND Ex are galvanically insulated from
each other as well as from '0 V DC'.
•
DC-powered units have 'DC +' and 'DC –' galvanically insulated from all other
clamps.
•
AC-powered units permit to tap the 24 V auxiliary voltage, which is also available
on '+24 Volt DC' (28) and '0 V DC' (39), from connections 'DC +'/'DC –' (clamps 4
and 5) too.
AC units therefore have a low-impedance connection between 'DC –' and GND an-
alog output via the '0 V DC' connection.
In contrast to the 24 V available on clamps 28 and 39, the auxiliary voltage on
'DC +'/'DC –' (clamps 4 and 5) is conducted through an internal extra common
mode filter and 'DC +' can be enabled/disabled by using the DC switch.
Fig. 14-3
Clamp wiring transmitter OCM F