All errors will be saved in the error memory (see chapter “21 Operation
Mode (RUN)“ subitem “Error messages”).
Fig. 23-24 Extended submenu analog output
Fig. 23-25 Error input mask
>Value at
errors<
Visible only if error mode has been enabled. This parameter is to de-
fine the desired analog output condition if an error should occur (see
also Fig. 23-26).
The following functions are available:
-
Hold old value (holds the last value prior to error)
-
Constant 0,0 mA
-
Constant 3,5 mA
-
Constant 4,0 mA
-
Constant 21,0 mA
Fig. 23-26 Programming error output
23.6 Parameter Menu “Relay”
Fig. 23-27 Menu relay
This menu allows defining both functions as well as accompanying parameters (such as limit
values, duration of impulse and more) of individual relay outputs. Select parameter >func-
tion< in order to indicate the available functions.
Toggle between relays using the >left< and >right< arrow keys.