QUICK GUIDE - EE210 MODBUS SETUP

(Full User‘s Guide at www.epluse.com/EE210)

E+E Elektronik Ges.m.b.H.

Langwiesen 7 • A-4209 Engerwitzdorf

Tel: +43 7235 605-0 • Fax: +43 7235 605-8

[email protected] • www.epluse.com

LG Linz Fn 165761 t • UID-Nr. ATU44043101

 

Place of Jurisdiction: A-4020 Linz • DVR0962759

BA_EE210_QGMS // v1.0 // Modification rights reserved // 302728

Address Switch

Address Switch

Slave address setting via EE-PCS Product Configuration Software:

All switches at position 0 → address has to be set via configuration software (factory setting 242).

Example: Slave address is set via configuration software.

Slave address setting via Dip-Switch:

Setting the Dip-Switch to any other address than 0 overwrites the slave address set via configuration software.

Example: Slave address set to 11 (=00001011 binary).

Protocol setting:

Address, baudrate, parity and stop bits can be set via: 

1. Configurator software (available on 

www.epluse.com/EE210

2. Modbus protocol (please see Application Note Modbus (available on 

www.epluse.com/EE210

0 0 0 0 0 0 0 0

1 1 0 1 0 0 0 0

FLOAT (read register):

Register

address

Communication

address

Parameter 

name

30026

0x19

temperature 

[°C], [°F]

30028

0x1B

relative humidity  

[%]

30030

0x1D

water vapour partial pressure  [mbar], [psi]

30032

0x1F

dew point temperature 

[°C], [°F]

30036

0x23

absolute humidity 

[g/m³], [g/ft³]

30038

0x25

mixing ratio 

[g/kg], [gr/lb]

30040

0x27

specific enthalpy 

[kJ/kg], [BTU/lb]

30042

0x29

frost point temperature 

[°C], [°F]

The measured values are saved as a 32Bit float value from 0x19 to 0x1F and from 0x23 to 0x29. Additionally the measured values 

are available as 16Bit signed integer from 0x12C to 0x12F and from 0x131 to 0x134. 

The factory setting for the Slave-ID (Modbus address) is 242 as an integer 16Bit value. This ID can be changed by the user in the 

register 60001 (0x00), permitted values are 1 - 247 permitted.

The serial number as ASCII-code is located at register address 30001-30008 (16Bit per address).

The Firmware version is located at register address 30009 (Bit 15...8 = major release; Bit 7...0 = minor release).

The choice of measurement units (metric or not metric) must be done in the ordering guide, see EE210 data sheet.

Switching from metric to non metric or vice versa by using the EE-PCS is not possible.

INTEGER (read register):*

Register

address

Communication

address

Parameter 

name

30301

0x12C

temperature 

[°C], [°F]

30302

0x12D

relative humidity  

[%]

30303

0x12E

water vapour partial pressure  [mbar], [psi]

30304

0x12F

dew point temperature 

[°C], [°F]

30306

0x131

absolute humidity 

[g/m³], [g/ft³]

30307

0x132

mixing ratio 

[g/kg], [gr/lb]

30308

0x133

specific enthalpy 

[kJ/kg], [BTU/lb]

30309

0x134

frost point temperature 

[°C], [°F]

* Values are stored with a scaling of 1:100 (e.g.: 2550 is equivalent to 25.5°C)

INTEGER (write register):*

Register

address

Communication

address

Parameter 

name

60001

0x00

Slave-ID (modbus addresse)

60002

0x01

Modbus protocol settings*

*For Modbus protocol setting please see Application Note Modbus 

 

(www.epluse.com/EE210)

INFO (read register):

Register

address

Communication

address

Parameter 

name

30001

0x00

Serial number

30009

0x08

Firmware version

MODBUS MAP