Assembly of Combi 302 Polar
When mounting the Combi 302 Polar future service and maintenance should be consid-
ered.
It is recommended to have minimum 60 and 30 cm free space in front of- and at the end
of the plant.
The system must be level due to the condense outlet. The condense outlet requires a clearance
height of minimum 11.5 cm under the outlet connection piece.
It is not necessary to re-insulate the system as it is delivered with a 20 mm standard insulation.
The system is low-noise and low-vibration. However, potential vibrations spreading from the sys-
tem to the individual building parts must be taken into account. We recommend a minimum
distance of 30 mm from building parts and other fixtures. It is recommended to place the plant on
vibration absorbers to separate the plant and the base
Figure 2: Mounting the Combi 302 Polar