background image

 

 

This document may be subject to change    

 

 

Side 6 of 24

 

Condensation drain / water seal 

The  Combi 302 Polar  unit is delivered with a 20mm condensation drain. (PVC, GF-fittings). The 
drain is placed under the discharge. 
 

 

The condensation drain should be carried with an even inclination of at least 1 cm per 
meter, frost-proof to the nearest outlet. The overflow from the safety valve should also be 
carried to the nearest outlet. 
 

 

 

To avoid frost problems it can be necessary to supply the condensation drain with a 
heating cable. It is the plumbers’ responsibility to secure the drain. 

 
 
When the system is running, there can be a vacuum of up to 500Pa (corresponding to 50mm water 
column) in the outlet. For this reason, the difference in height in the water seal must be minimum 
50mm. This means that the first bend of the water seal must be at least twice as long in order for 
the system to be able to dispose of the condense water (see figure 3). 
 
 
The condensation drain must be airproof from the unit to the water seal in order for the condensa-
tion water to be let away from  the unit. If the condensation drain is not airproof false air will be 
sucked in to the unit and the water will stay inside the unit. 
 
The water seal can dry out and avoid the water from running out of the unit. Therefore the water 
seal should be tested regularly and refilled with water if necessary. An elevated height of the water 
seal will reduce the need for refilling with water. 
 

min. 112

mm

min. 50 mm.

min. 50 mm.

Ø 20 mm drain

Unit

 

Figure 3: Condensation drain / water seal 

 

 

The water seal should be tested as described below. (the unit must be connected to the 
ducting and the front door should be closed):  
 
The condensation tray is filled with water and the unit is started at the highest ventilation 
step. The unit should run for a couple of minutes. Check that the condensation tray is 
empty when the test is finished. 

Содержание Combi 302 Polar Top

Страница 1: ...Version 10 00 28 11 2016 Combi 302 Polar Installation instruction CTS 602 by Nilan...

Страница 2: ...re parts 24 Figure table Figure 1 CTS 602 control 4 Figure 2 Mounting the Combi 302 Polar 5 Figure 3 Condensation drain water seal 6 Figure 4 Insulation of ducting 7 Figure 5 CTS 602 control 8 Figure...

Страница 3: ...elivery of the Combi 302 Polar is with filter classes F5 EU5 in the exhaust device and F7 EU7 in the injection The unit can be equipped with different accessories e g hygrostat and filter box with pol...

Страница 4: ...eler prevents fur ther cooling of the building if the primary heat supply stops by stopping the ventilation if the panel feeler gets below a specific value Factory setting is 10 C the value can be set...

Страница 5: ...es a clearance height of minimum 11 5 cm under the outlet connection piece It is not necessary to re insulate the system as it is delivered with a 20 mm standard insulation The system is low noise and...

Страница 6: ...ice as long in order for the system to be able to dispose of the condense water see figure 3 The condensation drain must be airproof from the unit to the water seal in order for the condensa tion wate...

Страница 7: ...ers of 50mm If the ducts are laid out in an unheated room it will cause condensation problems if the unit are turned off for a longer period of time as the hot air from the heated room will rise to th...

Страница 8: ...gh the service menu of the CTS 602 control For daily use of the CTS 602 control please see the CTS 602 directions delivered together with the Combi 302 Polar Use of t he CTS 600 panel pr ess ESC t o g...

Страница 9: ...isplay Press ENTER to activate the SERVICE menu It is then possible to scroll through the SERVICE menu options using the p buttons The options available on the SERVICE menu are shown in the figure bel...

Страница 10: ...ough the menus or to adjust the setting of an activated menu option ENTER to activate a menu option ENTER to confirm a menu option setting OFF switch off the controls ON to switch on the controls DEFR...

Страница 11: ...ROL PRESET OFF RESTART OFF ROOM CONTROL AIR EXCHANGE INLET HEATING AIR QUALITY MANUAL OFF MODBUS ADR 30 DATALOG INTV 10 Forsinkelse fra opstart af bl sere og varmekrav til eftervarmefladen frigives 0...

Страница 12: ...menus or to adjust the setting of an activated menu option ENTER to activate a menu option ENTER to confirm a menu option setting OFF switch off the controls ON to switch on the controls DEFROST FUNCT...

Страница 13: ...u option ENTER to confirm a menu option setting OFF switch off the controls ON to switch on the controls Each ventilation step can be set as a percentage of maximum fan INLET HEATING AIR EXCHANGE ENTE...

Страница 14: ...ST ENTER AIR EXCHANGE INLET CONTROL SERVICE ENTER TEMP CONTROL RESTART OFF MANUAL OFF PRESET OFF ROOM CONTROL AIR QUALITY MODBUS ADR 30 DATALOG INTV 10 HEAT SURFACE Lockout between 2 defrost periods C...

Страница 15: ...MP CONTROL ENTER AIR EXCHANGE DEFROST INLET CONTROL SERVICE ENTER RESTART OFF MANUAL OFF PRESET OFF ROOM CONTROL EXTERNAL 1 C AIR QUALITY Option for an extra heating element via relay output R8 R8 is...

Страница 16: ...through the menus or to adjust the setting of an activated menu option ENTER to activate a menu option ENTER to confirm a menu option setting OFF switch off the controls ON to switch on the controls I...

Страница 17: ...a menu option ENTER to confirm a menu option setting OFF switch off the controls ON to switch on the controls INLET HEATING ROOM CONTROL TEMP CONTROL AIR EXCHANGE DEFROST INLET CONTROL SERVICE ENTER R...

Страница 18: ...s through the menus or to adjust the setting of an activated menu option ENTER to activate a menu option ENTER to confirm a menu option setting OFF switch off the controls ON to switch on the controls...

Страница 19: ...activated menu option ENTER to activate a menu option ENTER to confirm a menu option setting OFF switch off the controls ON to switch on the controls INLET HEATING AIR EXCHANGE DEFROST INLET CONTROL...

Страница 20: ...witch off the controls ON to switch on the controls AIR QUALITY AIR EXCHANGE DEFROST INLET CONTROL SERVICE ENTER TEMP CONTROL PRESET OFF ROOM KONTROL RESTART OFF MANUAL OFF MANUAL OFF ENTER MANUAL DEF...

Страница 21: ...s or to adjust the setting of an activated menu option ENTER to activate a menu option ENTER to confirm a menu option setting OFF switch off the controls ON to switch on the controls AIR QUALITY AIR E...

Страница 22: ...ariables Din and Dout Options that flash are indicated by On the CTS602 control panel press ESC to return to the previous menu p to scroll upwards or downwards through the menus or to adjust the setti...

Страница 23: ...This document may be subject to change Side 23 of 24 System dimension Combi 302 Polar 1 Aussenluft 2 Zuluft 3 Abluft 4 Fortluft 10 Stromversorgung 11 Kondens Ablauf Figure 20 System dimension...

Страница 24: ...This document may be subject to change Side 24 of 24 Accessories spare parts Combi 302 Polar Filter types Qty Nilan item no Filter sheet G4 8 pcs 1 391713 Filter cassette F7 1 39520...

Отзывы: