Room control
The ROOM CONTROL menu allows the room temperature controller to be set.
Options that flash are indicated by
” ”
Parameters in the ROOM CONTROL menu should only be set by experienced control
technicians.
On the CTS602 control panel, press:
- ESC to return to the previous menu
-
p
to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
INLET
HEATING
ROOM
CONTROL
TEMP.
CONTROL
AIR
EXCHANGE
DEFROST
INLET
CONTROL
SERVICE
ENTER
RESTART
OFF
MANUAL
OFF
PRESET
OFF
AIR
QUALITY
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
ENTER
RESPONSE
NORMAL
RESPONSE
”USER”
RESPONSE
”FAST”
RESPONSE
”NORMAL”
GAIN
6.0°/°
INTERGRAL
6m
RESPONSE
”SLOW”
ENTER
N-ZONE
2.0°C
ENTER
RESPONSE
USER
N-ZONE
2.0°C
The RESPONSE
menu is only
accessible when the
CTS control is
set up to heating
surface
Rum control parametres:
Response
Gain
Integral
Slow
4.0
12
Normal
6.0
6
Fast
8.0
4
User
6.0
6
Figure 14: The "Room control" Menu