This document may be subject to change
Side 18 of 24
Restart
The RESTART menu allows the system to be set to restart automatically in connection with high or
low pressure faults.
Fire alarms can be acknowledged automatically in connection with fire drills/testing. A condition for
acknowledgement is that the fire thermostat input has returned to normal state.
Options that flash are indicated by
” ”
The ”HP/LP” setting in the RESTART menu must not be used during normal operation.
On the CTS602 control panel, press:
- ESC to return to the previous menu
-
p
to scroll upwards or downwards through the menus or to
adjust the setting of an activated menu option
- ENTER to activate a menu option
- ENTER to confirm a menu option setting
- OFF switch off the controls
- ON to switch on the controls
AIR
QUALITY
AIR
EXCHANGE
DEFROST
INLET
CONTROL
SERVICE
ENTER
TEMP.
CONTROL
MANUAL
OFF
PRESET
OFF
ROOM
CONTROL
RESTART
OFF
INLET
HEATING
MODBUS
ADR 30
DATALOG
INTV 10
HEAT
SURFACE
This setting must
never
be
used during normal
operation. Indicates that
the system is to be
restarted automatically in
connection with high or
low pressure alarms.
ENTER
RESTART
”HP/LP”
RESTART
”OFF”
Indicates that the system
will
not
be restarted
automatically in
connection with high or
low pressure alarms.
RESTART
”FIRE”
CLwE:Even weceipt
when fire input is back
to normal
Figure 15: The "Restart" Menu