DISPLAY AND MENU OPTIONS
Table 10. Smart DC Controller - Installer Menu Functions
Ref.
No.
User Menu
Display
Setting Options
(Bold = Factory
Settings)
Menu Tasks and Explanations
DC Controller
Display
Connections
25
S1 0
SENSOR #1 TYPE
0 - disabled
1 - (NOT USED)
2 - (EYE CLOSE)
3 - (EDGE CLOSE
4 - (EYE OPEN)
5 - (EDGE OPEN)
6 - (EDGE BOTH)
7 - (EYE BOTH)
UL 325 - 2018 sensor input setting
for external entrapment protection
sensor monitoring. All three sensor
types must be configured to a
non-zero number before the gate
operator will move the gate. Edge
Both is only available in Swing Gate
operator types. Eye Both is only
available in Slide Gate operator
types.
26
S2 0
SENSOR #2 TYPE
Same as Sensor 1 Same as Sensor 1
27
S3 0
SENSOR #3 TYPE
Same as Sensor 1 Same as Sensor 1
28
DT 0 FREE EXIT
DISABLE FUNCTION
0 = Disable Free
Exit
1 = Disable
Close Timer
Con
fi
gures BLOCK EXIT input to
disable either Free Exit Detector
function or, alternately, Close
Timer function. Default setting
disables free exit detector.
NOTE:
Free exit is disabled when
gate is at its closed limit. If closed
limit is not tripped, free exit
continues to work normally.
BLOCK EXIT COM
29
OR 1 REVERSE
OUTSIDE OBS LOOP
0 = Pause closing
only
1 = Enable
reversing to
open
Default is for full reversal when
Outside Obstruction Loop is
triggered while closing. A setting
of 0 causes gate to only pause
when triggered. Gate closure
continues as soon as loop is clear
again.
OUTSIDE OBS
LOOP COM or
Hy5B
MX4505 Rev. E ©2020
66
hysecurity.com | 800-321-9947
SlideSmart DC Programming and Operations