221 - LP ALARM
Is the low pressure transmitter
correctly connected?
YES
YES
Is the value around 0 MPa, without
significant change, both in states
(1) and (2)?
Connect a pressure gauge to the
low pressure pipe and measure in
state (1). Compare with the value
shown on the indoor module.
Action.
Check the value on the low
pressure transmitter, via indoor
module, in: (1) stationary
compressor, (2) compressor
operation.
Replace the low pressure
transmitter.
NO
NO
Is the difference less than 0.2
MPa?
Advance to checking the
refrigerant circuit on the next
page.
Connect a new low pressure
transmitter to the control board
and position it open in the
atmosphere.
YES
NO
Is the pressure 0 MPa in the
indoor module?
Replace the control board.
Replace the low pressure
transmitter.
YES
NO
47