May be due to
Description
Alarm text on
the display
Alarm
- Sensor does not work (see "Temperature
sensor" section)
Temperature deviation on the heat exchanger
sensor (Tho-R1/R2) 5 times within 60 minutes
or for 60 minutes continuously
High HX temp
261
- Insufficient air circulation or blocked evaporator
- Defective control board in AMS 10
- Too much refrigerant
Also see the troubleshooting guide on page
Can occur when the 15V power supply to the
inverter is unstable.
The inverter module has activated the alarm for
high temperature 5 times within 60 minutes
Inverter error
262
- Incoming power supply interference
Voltage from the inverter outside the paramet-
ers 4 times within 30 minutes
Inverter error
263
- Service valve closed
- Insufficient amount of refrigerant
- Compressor fault
- Defective circuit board for inverter in AMS 10
Also see the troubleshooting guide on page
- Open-circuit in connection between boards
Communication between circuit board for invert-
er and control board broken 3 times in at least
15 seconds
Inverter error
264
- Defective circuit board for inverter in AMS 10
- Defective control board in AMS 10
Also see the troubleshooting guide on page
- Defective fan motor
Continuous deviation on power transistor for
15 minutes.
Inverter error
265
- Defective circuit board for inverter in AMS 10
Also see the troubleshooting guide on page
- Service valve closed
Insufficient refrigerant has been detected at
start-up in cooling operation. 1 minute after
start-up, BT15 must have decreased 4K com-
pared to BT3.
Insufficient refri-
gerant
266
- Loose connection sensor (BT15, BT3)
- Defective sensor (BT15, BT3)
- Too little refrigerant
Also see the troubleshooting guide on page
- Defective circuit board for inverter in AMS 10
Failed start for compressor
Inverter error
267
- Defective control board in AMS 10
- Compressor fault
Also see the troubleshooting guide on page
- Sudden power failure
Overcurrent to inverter 4 times within 30
minutes
Inverter error
268
Also see the troubleshooting guide on page
- Open-circuit or short-circuit on sensor input
The input for the sensor receives unreasonably
high or low value 3 times within 40 minutes
Sensor fault Tho-
R
277
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
Also see the troubleshooting guide on page
- Open-circuit or short-circuit on sensor input
The input for the sensor receives unreasonably
high or low value 3 times within 40 minutes
Sensor fault Tho-
A
278
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
Also see the troubleshooting guide on page
- Open-circuit or short-circuit on sensor input
The input for the sensor receives unreasonably
high or low value 3 times within 40 minutes
Sensor fault Tho-
D
279
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
Also see the troubleshooting guide on page
NIBE AMS10
Chapter 6 | Troubleshooting
44