Page 62
4.
Verify that the Climate screens for the zones are not displaying “Wait” and that the white flame or
fan icons are not displayed.
If the icons are being displayed and the heat pump will not run, then the problem most likely is on
the Dometic control side.
If the A/Cs won’t run:
1.
Verify that the Zone(s) are calling for cool and that the set points are lower than the Zone(s) ambient
temperature.
If not, then adjust the settings accordingly.
2.
Verify that AC power is available and that the circuit breakers are not tripped.
Reset the breakers if tripped.
3.
Verify that the Climate screens for the zones are not displaying “Wait” and that the white snowflake
or fan icons are not displayed.
If the icons are being displayed and the heat A/Cs will not run, then the problem most likely is on
the Dometic control side.
Oasis System Issues
It is important to determine if the fault lies in the SilverLeaf or the Oasis control system.
If the Oasis Burner will not Light:
1.
Verify that the Oasis button is highlighted.
If not, then press the Oasis button.
2.
If the Burner still does not light, then plug in the Oasis Remote Control in place of the SilverLeaf
Control and set the Burner Switch to on.
If the Burner still does not light, then the problem lies in the Oasis system.
If the Oasis Burner will not stay On:
1.
Verify that the Oasis button is highlighted.
If not, then press the Oasis button.
2.
If the Burner command turns off by its self, then verify that the software version for the OA600
(Oasis) Control Board is correct.
If the software version is not correct, then update the software to the correct version.
If the Oasis AC Heating Elements will not turn On:
1.
Verify that the AC #1 and or AC #2 buttons are highlighted either Blue (On) or Yellow (Shed).
If not, then press one or both AC buttons.
2.
If either AC button is highlighted yellow, then the Oasis coolant is at temperature, the Heater Coil is
shed or there is no AC power available.
A.
To determine if the Oasis coolant is at temperature, turn on a hot water tap until the water
temperature drops. If the AC button turns blue, then the Heater coil is working correctly.
Содержание SilverLeaf RV-C Control System
Страница 1: ...2012 Newmar Corporation October 2011 SilverLeaf RV C Control System Training Manual ...
Страница 2: ......
Страница 41: ...Page 39 ALL ELECTRIC OPTION LP STANDARD ...
Страница 42: ...Page 40 All Electric Option LPG Tank Set to Off LP Standard LPG Tank Set to On ALL ELECTRIC OPTION LP STANDARD ...
Страница 43: ...Page 41 ...
Страница 44: ...Page 42 ...
Страница 45: ...Page 43 EXDP TANK CAPACITIES KGDB TANK CAPACITIES ...
Страница 46: ...Page 44 ...
Страница 47: ...Page 45 ...
Страница 48: ...Page 46 ...
Страница 49: ...Page 47 ...
Страница 50: ...Page 48 ...
Страница 51: ...Page 49 ...
Страница 52: ...Page 50 ...
Страница 53: ...Page 51 ...
Страница 54: ...Page 52 ...
Страница 55: ...Page 53 ...
Страница 56: ...Page 54 ...
Страница 57: ...Page 55 ...
Страница 58: ...Page 56 ...
Страница 59: ...Page 57 ...
Страница 60: ...Page 58 Blank Page ...