: The Auto Fill function will timeout if the tank does not fill fast enough. This is because the control
system assumes that there is a leak in the tank fill plumbing and turns off the Auto Fill after the
timeout interval.
Generator Issues
If the Generator will not Start from the remote switches
1.
Verify that the Generator will start from the switch located on the generator housing.
If the Generator will not start directly from the generator switch, then the problem resides in
the generator. Correct the generator issue and retest.
2.
Verify that the Generator will start from the Touch Screen.
If the Generator will not start, then verify that the Generator Harness is correctly connected at
the TM-102 and the Generator. Correct the wiring as required, then retest that the Generator
will start from the Touch Screen.
3.
If the Generator will start from the Touch Screen, then verify that the remote switch (Dash, etc.)
wiring is correct and that the switch is supplying a ground signal to the TM-102 Input 2.
Correct any generator wiring issues and retest the Generator remote start/stop functions.
4.
If the Generator will not start from the Touch Screen, and you have completed the previous test,
then verify the TM-102 configuration.
Correct the configuration as required and retest generator start/stop function.
5.
If the Generator still will not start, then the problem most likely is in the TM-102 Module.
Replace the Module and retest the Generator start/stop function.
If the Generator will not start from the Touch Screen
1.
See the previous section for corrective actions.
If the Generator will not Auto Start
1.
Verify that the Generator Auto Start Function(s) are Enabled and the Trigger Point values are set
correctly. Verify that the Safety Lock function is off and retest Auto Start Function.
If the Generator Auto Start Function still fails, then see “If the Generator will not Start from the
remote switches” section for corrective actions.
Содержание SilverLeaf RV-C Control System
Страница 1: ...2012 Newmar Corporation October 2011 SilverLeaf RV C Control System Training Manual ...
Страница 2: ......
Страница 41: ...Page 39 ALL ELECTRIC OPTION LP STANDARD ...
Страница 42: ...Page 40 All Electric Option LPG Tank Set to Off LP Standard LPG Tank Set to On ALL ELECTRIC OPTION LP STANDARD ...
Страница 43: ...Page 41 ...
Страница 44: ...Page 42 ...
Страница 45: ...Page 43 EXDP TANK CAPACITIES KGDB TANK CAPACITIES ...
Страница 46: ...Page 44 ...
Страница 47: ...Page 45 ...
Страница 48: ...Page 46 ...
Страница 49: ...Page 47 ...
Страница 50: ...Page 48 ...
Страница 51: ...Page 49 ...
Страница 52: ...Page 50 ...
Страница 53: ...Page 51 ...
Страница 54: ...Page 52 ...
Страница 55: ...Page 53 ...
Страница 56: ...Page 54 ...
Страница 57: ...Page 55 ...
Страница 58: ...Page 56 ...
Страница 59: ...Page 57 ...
Страница 60: ...Page 58 Blank Page ...