NEOMERIS CONTROL DES
Appendix
Build:20211025-094624-9873335NSt
All information and technical data are subject to
change
Page 76
»Contact Type
(Sel.)
NEOMERIS CONTROL DES, Device, Bleed
off, Bleedoff Valve Control
0
active=ener-
gized
-
1
active=not en-
ergized
-
Measure Res.
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Measuring resolution of water amount (impuls
per liter)
Range:
0.001 ... 999.999 pls/Ltr
Default:
1.000 pls/Ltr
Measure Res.
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Measuring resolution of water amount (liter per
impuls)
Range:
0.001 ... 99.999 Ltr/pls
Default:
1.000 Ltr/pls
Units
(Sel.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Choice of the measurement resolution
Default:
Pls/Ltr
0 Pls/Ltr
-
1 Ltr/Pls
-
Minim. flow
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Minimal working reach of the flow
Range:
1 ... 32767 l/h
Default:
400 l/h
Maxim. flow
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Maximal working reach of the flow
Range:
0 ... 32767 l/h
Default:
5000 l/h
Mesrg. Method
(Sel.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Measuring method(process controlled,
pulscount or pulslength)
Default:
Counter
0 Automatic
-
1 Counter
-
2 Puls Length
-
Gate Time
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Time periode for counting of impulses
Range:
0 ... 9999999 ms
Default:
1000 ms
Debounce
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Stabilisation time of impuls
Range:
0 ... 999 ms
Default:
10 ms
»Min(Warn.)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Warning low limit
Range:
0 ... 32767 l/h
Default:
0 l/h
»Min(Alarm)
(Num.)
NEOMERIS CONTROL DES, Device, Bleed
off, Blowd. flow
Alarm low limit
Range:
0 ... 32767 l/h
Default:
0 l/h
Warning high limit