NEOMERIS CONTROL DES
Functional description
Build:20211025-094624-9873335NSt
All information and technical data are subject to
change
Page 49
6.13
Module: MTankAlarms
6.13.1 Info:
Tank using 2 Alarms
6.13.2 Comment:
The controller can manage a tank with one or two sensors.
For the tank level sensor full or low, the contact type (occupied / n.occupied) can be set.
Debouncing during filling ensures that the sensor does not deflect directly when the level changes,
but waits for a certain time to prevent false readings from moving liquid.
The parameter Tank type can be used to set whether the tank has an overflow or not.
6.13.3 Internal elements of module:
6.13.3.1 Parameters
»Contact Up
(Sel.)
Kind of contact (used/n.used)
Default:
occupied=active
0 occupied=active
-
1 not occupied=active
-
»Contact Low
(Sel.)
Kind of contact (used/n.used)
Default:
occupied=active
0 occupied=active
-
1 not occupied=active
-
»Debouncing Fill
(Num.)
Delay to accept the tank level
Range:
0.0 ... 99.9 s
Default:
2.0 s
6.13.3.2 Digital input (DI)
»Level Full
DI(High-Level sensor).
0 OFF Switched Off / Inactive
1 ON
Switched On / Active
»DosProp.1 Tank empty
eB1: 23=Di2, 24=GND (Digital-Input 2)
0 OFF Switched Off / Inactive
1 ON
Switched On / Active